Baxi heat pump error codes

Baxi · An established brand in the UK. 265 codes across 5 product families, each taken from the manufacturer’s manuals. Baxi technical support ↗

Find a Baxi engineer →265 codes · reviewed 23 September 2026

Filter by product family

Type the code on your display or a word from its meaning. Each code opens its own page with what it means, whether it is safe and what you can check.

265 codes

CodeMeaningStops?Homeowner check?
A00.32
TOutside Open Outside temperature sensor is either removed or measures a temperature below range
NoYes
A00.33
TOutside Closed Outside temperature sensor is either shorted or measures a temperature above range
NoYes
A00.34
TOutside Missing Outside temperature sensor was expected but not detected
NoYes
A1
Display reads A1 with audible alarm
Not statedYes
A02.06
Water Press Warning Water Pressure Warning active
NoYes
A02.18
OBD Error Object Dictionary Error
NoYes
A02.22
System flow warning System water flow warning active
NoYes
A02.37
Uncritic device lost Uncritical device has been disconnected:
NoYes
A02.55
Inval or miss SerNR Invalid or missing device serial number
NoYes
A02.80
Missing Cascade Ctrl Missing Cascade controller
NoYes
A06.111
HP unit failure Heat Pump unit failure occurred
NoYes
A06.112
HP EEPROM error Hydronic system EEPROM error in the heat pump module
NoYes
A06.113
HP frost protection Water side heat exchanger frost protection
NoYes
A06.114
HP flow Temp error Flow temperature sensor error in the heat pump module
NoYes
A06.115
HP EEPROM error Heat pump inverter module EEPROM error
NoYes
A06.116
Water flow error Water flow is not detected by the heat pump module
NoYes
A06.117
ODU backup error Electric heating plate relay adhesion failure in the internal backup heater PCB
NoYes
A06.118
ODU current error Current transformer error or internal backup heater open circuit protection
NoYes
A10.45
RoomTempZoneA miss Measure of Room Temperature Zone A is missing
NoYes
A10.46
RoomTempZoneB miss Measure of Room Temperature Zone B is missing
NoYes
A10.47
RoomTempZoneC miss Measure of Room Temperature Zone C is missing
NoYes
A10.50
T_DHW top D miss Domestic Hot Water temperature sensor top zone DHW is missing
NoYes
A10.54
Temp. Zone DHW miss. Temperature sensor Zone DHW is missing
NoYes
A10.56
T_DHW Zone AUX miss Domestic Hot Water temperature sensor Zone AUX is missing
NoYes
bA
T4 sensor out of operation range protection
NoYes
bH
PED PCB failure
YesYes
C7
Transducer module temperature too high protection
YesYes
CL
Water pump communication wire fault
Not statedYes
E0
Flow switch error (E8 displayed 3 times)
YesYes
E00.00
TFlow Open Flow temperature sensor is either removed or measures a temperature below range
YesYes
E00.01
TFlow Closed Flow temperature sensor is either shorted or measures a temperature above range
YesYes
E1
Phase sequence fault (three-phase unit only)
Not statedYes
E2
Communication error between user interface and main control board of hydraulic module
Not statedYes
E02.13
Blocking Input Blocking Input of the Control Unit from device external environment
YesYes
E02.24
System flow locking System water flow locking active
YesYes
E3
Backup heater exchanger outlet water temperature sensor (T1) error
Not statedYes
E4
Domestic hot water temperature sensor (T5) error
Not statedYes
E5
Condenser outlet refrigerant temperature sensor (T3) error
Not statedYes
E6
Ambient temperature sensor (T4) error
Not statedYes
E06.03
Locking HydrauBackup Locking Hydraulic Backup
YesYes
E06.110
HP flow error Water flow error active in the heat pump module
YesYes
E7
Buffer tank up temp. sensor (Tbt1) fault
Not statedYes
E8
Water flow failure
Not statedYes
E9
Suction temperature sensor (Th) error
Not statedYes
EA
Discharge temperature sensor (Tp) error
Not statedYes
Eb
Solar temp. sensor (Tsolar) fault
Not statedYes
Ec
Buffer tank low temp. sensor (Tbt2) fault
Not statedYes
Ed
Inlet water temperature sensor (Tw_in) error
Not statedYes
EE
Main control board of hydraulic module EEprom failure
Not statedYes
EL
Communication fault between hydraulic module and MH kit
Not statedYes
F1
DC generatrix (DC bus) voltage too low
YesYes
F6
EXV (electronic expansion valve) fault
Not statedYes
F75
Insufficient discharge superheating
Not statedYes
FC1
TL outdoor unit heat exchanger outlet temperature sensor error
Not statedYes
H0
Communication error between main control board PCB B and main control board of hydraulic module
Not statedYes
H00.16
DHW sensor Open Domestic Hot Water tank temperature sensor is either removed or measures a temperature below range
PartlyYes
H00.17
DHW sensor Closed Domestic Hot Water tank temperature sensor is either shorted or measures a temperature above range
PartlyYes
H00.32
TOutside Open Outside temperature sensor is either removed or measures a temperature below range
PartlyYes
H00.33
TOutside Closed Outside temperature sensor is either shorted or measures a temperature above range
PartlyYes
H00.34
TOutside Missing Outside temperature sensor was expected but not detected
PartlyYes
H00.47
HP flow sensor removed or below range
PartlyYes
H00.48
THp Flow Closed Heat pump flow temperature sensor is either shorted or measures a temperature above range
PartlyYes
H00.49
THp Flow Missing Heat pump flow temperature sensor was expected but not detected
PartlyYes
H00.51
THp Return Open Heat pump return temperature sensor is either removed or measures a temperature below range
PartlyYes
H00.52
THp Return Closed Heat pump return temperature sensor is either shorted or measures a temperature above range
PartlyYes
H00.57
T DHW Top Open Domestic Hot Water top temperature sensor is either removed or measures a temperature below range
PartlyYes
H00.58
T DHW Top Closed Domestic Hot Water top temperature sensor is either shorted or measures a temperature above range
PartlyYes
H00.69
TbufferTankOpen Buffer Tank temperature sensor is either removed or measures a temperature below range
PartlyYes
H00.70
TbufferTankClosed Buffer Tank temperature sensor is either shorted or measures a temperature above range
PartlyYes
H00.71
TbufferTankTopOpen Buffer Tank top temperature sensor is either removed or measures a temperature below range
PartlyYes
H00.72
TbufferTankTopClosed Buffer Tank top temperature sensor is either shorted or measures a temperature above range
PartlyYes
H00.74
TBufferTankMissing Buffer Tank temperature sensor was expected but not detected
PartlyYes
H00.75
TBufferTankTop Miss Buffer Tank Top temperature sensor was expected but not detected
PartlyYes
H00.76
TcascadeFlow Open Cascade Flow temperature sensor is either removed or measures a temperature below range
PartlyYes
H00.77
TcascadeFlow Closed Cascade Flow temperature sensor is either shorted or measures a temperature above range
PartlyYes
H00.78
TcascadeFlow missing Cascade Flow temperature sensor was expected but not detected
PartlyYes
H1
Communication error between inverter module PCB A and main control board PCB B
YesYes
H2
Plate heat exchanger refrigerant inlet (liquid pipe) temperature sensor (T2) error
Not statedYes
H02.02
Wait Config Number Waiting For Configuration Number
PartlyYes
H02.03
Conf Error Configuration Error
PartlyYes
H02.04
Parameter Error Parameter Error
PartlyYes
H02.05
CSU CU mismatch CSU does not match CU type
PartlyYes
H02.07
Water Press Error Water Pressure Error active
PartlyYes
H02.09
Partial block Partial blocking of the device recognized
PartlyYes
H02.10
Full Block Full blocking of the device recognized
PartlyYes
H02.16
Int CSU Timeout Internal CSU Timeout
PartlyYes
H02.23
System flow error System water flow error active
PartlyYes
H02.25
ACI error Titan Active System short circuited or on an open circuit
PartlyYes
H02.36
Funct device lost Functional device has been disconnected
PartlyYes
H02.37
Uncritic device lost Uncritical device has been disconnected
PartlyYes
H02.40
Function unavailable Function unavailable
PartlyYes
H02.45
Full Can Conn Matrix Full Can Connection Matrix
PartlyYes
H02.46
Full Can Device Adm Full Can Device Administration
PartlyYes
H02.47
Failed Conn Funct Gr Failed Connecting Function Groups
PartlyYes
H02.48
Funct Gr Conf Fault Function Group Configuration Fault
PartlyYes
H02.49
Failed Init Node Failed Initialising Node
PartlyYes
H02.55
Inval or miss SerNR Invalid or missing device serial number
PartlyYes
H02.60
Unsupported function The zone doesn't support the selected function
PartlyYes
H02.61
Unsupported function Zone A doesn't support the selected function
PartlyYes
H02.62
Unsupported function Zone B doesn't support the selected function
PartlyYes
H02.63
Unsupported function Zone C doesn't support the selected function
PartlyYes
H02.64
Unsupported function Zone D doesn't support the selected function
PartlyYes
H02.65
Unsupported function Zone E doesn't support the selected function
PartlyYes
H02.66
TAS not connected The anti corrosion protection (TAS) of the Domestic Hot Water tank is not connected
PartlyYes
H02.67
TAS short-circuit The anti corrosion protection (TAS) of the Domestic Hot Water tank is shortend
PartlyYes
H3
Plate heat exchanger refrigerant outlet (gas pipe) temperature sensor (T2B) error
Not statedYes
H4
Three times P6 protection
YesYes
H5
Indoor temperature sensor (Ta) error
Not statedYes
H6
DC fan failure
Not statedYes
H06.01
HP Unit Failure Heat Pump Unit Failure occured
PartlyYes
H06.06
BL CompHighPressure A high pressure anomaly has stopped the compressor
PartlyYes
H06.07
BL CompLowPressure A low pressure anomaly has stopped the compressor
PartlyYes
H06.17
DeltaT CH max limit The Delta Temperature on the central heating side exceeds the maximum overshoot.
PartlyYes
H06.21
Tret heat pump Heat pump return temperature sensor error
PartlyYes
H06.22
Heating error Heating operation error
PartlyYes
H06.23
Refr pressure Refrigerant pressure sensor error
PartlyYes
H06.24
Refr high pressure The refrigerant high pressure protection is activated
PartlyYes
H06.25
Tflow heat pump Heat pump flow temperature sensor error
PartlyYes
H06.26
HP liquid temp Heat pump liquid temperature sensor error
PartlyYes
H06.27
Frost protection The heat pump frost protection is activated
PartlyYes
H06.28
Comm IDU - ODU Communication error between the indoor unit and outdoor unit
PartlyYes
H06.29
ODU-interface Mismatch between the outdoor unit and the interface board
PartlyYes
H06.30
ODU temperature The outdoor unit temperature is anomalous
PartlyYes
H06.31
ODU temp sensor Outdoor unit temperature sensor error
PartlyYes
H06.32
ODU temp sensor Outdoor unit temperature sensor error
PartlyYes
H06.33
ODU heatsink temp Outdoor unit heatsink temperature is anomalous
PartlyYes
H06.34
ODU power module Outdoor unit power module is anomalous
PartlyYes
H06.35
ODU superheat The outdoor unit superheat is anomalous
PartlyYes
H06.36
Fan motor Outdoor unit fan motor is anomalous.
PartlyYes
H06.37
Overheat protection The outdoor unit overheat protection is activated
PartlyYes
H06.38
ODU pressure The outdoor unit pressure is anomalous
PartlyYes
H06.39
ODU overcurrent Compressor overcurrent in the outdoor unit
PartlyYes
H06.40
ODU current sensor Current sensor error in the outdoor unit
PartlyYes
H06.41
ODU Tinl water The outdoor unit inlet water temperature is anomalous
PartlyYes
H06.42
ODU refrigerant Outdoor unit refrigerant is anomalous
PartlyYes
H06.43
DIP switch The DIP switch on the interface board has a configuration error interface panel = EHC–16 PCB
PartlyYes
H06.53
Tambiant air minimum The ambient air temperature is below the allowed minimum
PartlyYes
H06.58
HP outdoor temp Heat pump outdoor temperature sensor error
PartlyYes
H06.59
HP suction temp Heat pump compressor suction temperature sensor error
PartlyYes
H06.60
HP inverter voltage The inverter voltage of the heat pump is too low
PartlyYes
H06.61
HP supply voltage The heat pump power supply voltage is out of range
PartlyYes
H06.62
HP discharge temp Heat pump compressor discharge temperature sensor error
PartlyYes
H06.63
HP EEPROM error Heat pump Inverter module EEPROM error
PartlyYes
H06.64
HP inverter com Communication error between the outdoor main control unit and the inverter module of the heat pump
PartlyYes
H06.65
HP high temp cooling HP refrigerant outlet temperature is too high in cooling mode
PartlyYes
H06.66
HP gas temp Heat pump gas temperature sensor error
PartlyYes
H06.67
ODU return high flow The heat pump return temperature is higher than the flow temperature in the outdoor unit
PartlyYes
H06.68
ODU air temp sensor Refrigerant outlet temperature sensor error in air side of heat exchanger of the outdoor unit
PartlyYes
H06.69
3 phase sequence Invalid phase sequence in the 3 phase heat pump power supply
PartlyYes
H06.75
ODU flow error Water flow error active in the outdoor unit module
PartlyYes
H06.76
ODU return temp err Return temperature sensor is on error in the outdoor unit
PartlyYes
H06.77
ODU EEPROM error EEPROM error in hydronic system main control board in the outdoor unit
PartlyYes
H06.78
ODU internal com Err Communication error between refrigerant system and hydronic system main control boards
PartlyYes
H06.79
ODU flow temp err Flow temperature sensor is on error in the outdoor unit
PartlyYes
H06.80
HE frost protection ODU water side heat exchanger anti-freeze protection
PartlyYes
H06.81
Evaporator error Evaporator error in the outdoor unit
PartlyYes
H06.99
Compressor alarm Alarm related to the compressor raised by the inverter
PartlyYes
H7
Main circuit voltage failure
Not statedYes
H8
Pressure sensor failure
YesYes
H9
System outlet water temperature sensor T1B failure
Not statedYes
H10.00
T Flow Zone A Open Flow temperature sensor Zone A Open
PartlyYes
H10.01
T Flow Zone A Closed Flow temperature sensor Zone A Closed
PartlyYes
H10.02
T Dhw Zone A Open Domestic Hot Water temperature sensor Zone A Open
PartlyYes
H10.03
T Dhw Zone A Closed Domestic Hot Water temperature sensor Zone A Closed
PartlyYes
H10.04
TSwimmPoolZoneA Open Swimming Pool Temperature Sensor Zone A Open
PartlyYes
H10.05
TSwimmPoolZoneAClose Swimming Pool Temperature Sensor Zone A Closed
PartlyYes
H10.09
T Flow Zone B Open Flow temperature sensor Zone B Open
PartlyYes
H10.10
T Flow Zone B Closed Flow temperature sensor Zone B Closed
PartlyYes
H10.11
T Dhw Zone B Open Domestic Hot Water Temperature Sensor Zone B Open
PartlyYes
H10.12
T Dhw Zone B Closed Domestic Hot Water temperature sensor Zone B Closed
PartlyYes
H10.13
TSwimmPoolZoneB Open Swimming Pool Temperature Sensor Zone B Open
PartlyYes
H10.14
TSwimmPoolZoneBClose Swimming Pool Temperature Sensor Zone B Closed
PartlyYes
H10.18
T Flow Zone C Open Flow temperature sensor Zone C Open
PartlyYes
H10.19
T Flow Zone C Closed Flow temperature sensor Zone C Closed
PartlyYes
H10.20
T Dhw Zone C Open Domestic Hot Water Temperature Sensor Zone C Open
PartlyYes
H10.21
T Dhw Zone C Closed
PartlyYes
H10.22
TSwimmPoolZoneC Open Swimming Pool Temperature Sensor Zone C Open
PartlyYes
H10.23
TSwimmPoolZoneCClose Swimming Pool Temperature Sensor Zone C Closed
PartlyYes
H10.27
T Flow Zone DHW open Flow temperature sensor Zone DHW open
PartlyYes
H10.28
Sens. ZoneDHW closed Flow temperature sensor Zone DHW closed
PartlyYes
H10.29
Sensor Zone DHW open Temperature sensor Zone DHW open
PartlyYes
H10.30
T Zone DHW closed Domestic Hot Water temperature sensor Zone DHW closed
PartlyYes
H10.36
Sensor Zone AUX open Flow temperature sensor Zone AUX open
PartlyYes
H10.37
Sens. ZoneAUX closed Flow temperature sensor ZoneAUX closed
PartlyYes
H10.38
T Dhw Zone AUX open Domestic Hot Water temperature sensor Zone AUX open
PartlyYes
H10.39
Sens. ZoneAUX Closed Domestic Hot Water temperature sensor Zone AUX closed
PartlyYes
HA
Plate heat exchanger water outlet temperature sensor (TW_out) error
Not statedYes
Hb
Three times 'PP' protection and Tw_out < 7°C
YesYes
Hd
Communication fault between hydraulic module parallel (cascade master/slave)
Not statedYes
HE
Condenser refrigerant outlet temperature too high in heating mode for more than 10 minutes
YesYes
HF
Main control board PCB B EEprom failure
Not statedYes
HH
H6 displayed 10 times in 2 hours
YesYes
HL
PFC module fault
YesYes
HP
Low pressure protection (Pe<0.6) occurred 3 times in an hour
YesYes
J1E
Fan drive: hardware overcurrent protection
Not statedYes
J2E
Fan drive: overheating protection
Not statedYes
J3E
Fan drive: bus voltage too low error
Not statedYes
J5E
Fan motor failed to start
Not statedYes
J6E
Fan drive: phase loss protection
Not statedYes
J11
Fan drive: phase current instantaneous overcurrent protection
Not statedYes
J12
Fan drive: phase current continuous 30 s overcurrent protection
Not statedYes
J31
Fan drive: bus voltage too high error
Not statedYes
J32
Fan drive: bus voltage excessively high error
Not statedYes
J43
Fan drive: abnormal phase current sampling bias
Not statedYes
J45
Fan motor code mismatch error
Not statedYes
J46
Fan drive: IPM protection (FO)
Not statedYes
J52
Fan motor stalling protection
Not statedYes
J61
Fan terminal short circuit protection
Not statedYes
J65
Fan drive: IPM short circuit protection
Not statedYes
L0
Module protection (P6 group)
YesYes
L1
Display reads L1 with audible alarm
YesYes
L1E
Compressor drive: hardware overcurrent protection
Not statedYes
L2
DC generatrix high voltage protection (P6 group)
YesYes
L2E
Compressor drive: overheating protection
Not statedYes
L3E
Compressor drive: bus voltage too low error
Not statedYes
L4
MCE malfunction (P6 group)
YesYes
L5
Zero speed protection (P6 group)
YesYes
L5E
Compressor drive: motor failed to start
Not statedYes
L6E
Compressor drive: phase loss protection
Not statedYes
L7
Phase sequence fault (P6/L-group)
Not statedYes
L8
Speed difference >15Hz protection between the front and the back clock (P6 group)
YesYes
L9
Speed difference >15Hz protection between the real and the setting speed (P6 group)
YesYes
L11
Compressor drive: phase current instantaneous overcurrent protection
Not statedYes
L12
Compressor drive: phase current continuous 30 s overcurrent protection
Not statedYes
L31
Compressor drive: bus voltage too high error
Not statedYes
L32
Compressor drive: bus voltage excessively high error
Not statedYes
L34
Phase loss error on the three-phase power supply
Not statedYes
L43
Compressor drive: abnormal phase current sampling bias
Not statedYes
L45
Compressor drive: motor code mismatch error (printed 'Fan motor code mismatch error' in the L-series)
Not statedYes
L46
Compressor drive: IPM protection (FO)
Not statedYes
L47
Compressor drive: module type mismatch
Not statedYes
L52
Compressor drive: motor stalling protection
Not statedYes
L61
Compressor terminal short circuit protection
Not statedYes
L65
Compressor drive: IPM short circuit protection
Not statedYes
LB7
PED error
Not statedYes
LBE
Action of high pressure switch
Not statedYes
LC1
Instantaneous overcurrent of PFC software protection
Not statedYes
LC2
PFC software continuous 30 s overcurrent protection
Not statedYes
LC3
PFC low voltage protection
Not statedYes
LC4
PFC power factor is less than 0.8
Not statedYes
LC5
PFC valid value overcurrent protection
Not statedYes
LC6
PFC1 channel hardware overcurrent protection
Not statedYes
LC7
PFC2 channel hardware overcurrent protection
Not statedYes
LC8
PFC3 channel hardware overcurrent protection
Not statedYes
LC9
Overheating protection of PFC module
Not statedYes
LCA
PFC module CBC overcurrent error protection
Not statedYes
LCB
Overvoltage of PFC bus or PFC half bus
Not statedYes
LCC
Short circuit of PFC IGBT
Not statedYes
LCD
Abnormal PFC sampling bias
Not statedYes
LCE
PFC hardware overcurrent protection
Not statedYes
P0
Low pressure protection
YesYes
P1
High pressure protection
YesYes
P3
Compressor overcurrent protection
YesYes
P4
High discharge temperature protection
YesYes
P5
High temperature difference protection between water inlet and outlet of the plate heat exchanger
Not statedYes
P6
Module protection
YesYes
P9
DC fan motor protect
Not statedYes
P21
L-SEN low pressure sensor error
Not statedYes
P27
H-SEN and L-SEN connected in reverse (detected when the compressor is off)
Not statedYes
Pb
Anti-freeze mode protection
NoYes
Pd
High temperature protection of refrigerant outlet temp of condenser
YesYes
PE
Water pressure sensor failure
Not statedYes
PF
Water flow sensor failure
Not statedYes
PP
Water inlet temperature higher than water outlet in heating mode
Not statedYes
t1
Display reads t1 with audible alarm
YesYes