P5 on a Baxi heat pump: High temperature difference protection between water inlet and outlet of the plate heat exchanger
Short answer
On a Baxi heat pump, P5 means: High temperature difference protection between water inlet and outlet of the plate heat exchanger. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.
Reviewed 23 September 2026 · 3 sources
What it means
On the Assure Monobloc ASHP (Assure Mono 5/7/9/12/16)
The manual says: High temperature difference protection between water inlet and outlet of the plate heat exchanger.
Part involved: water flow / pressure.
Likely causes:
- Shut-off valves not fully open; filter needs cleaning; air in system; water pressure must be >1 bar (cold); pump speed; expansion vessel; circuit resistance too high.
On the HP40 / Baxi Assure HP50 Monobloc ASHP
The manual says: (Tw_out - Tw_in) value too big protection.
Part involved: water flow / pressure.
Likely causes:
- Shut-off valves not fully open; filter needs cleaning; air in system; water pressure must be >1 bar; pump speed; expansion vessel; circuit resistance too high for pump.
On the HP60 / Baxi Assure HP55 High Temperature Monobloc ASHP (R290)
The manual says: Abnormal temperature difference between the water outlet and inlet temperature.
Part involved: water flow / pressure.
Is it safe?
On the Assure Monobloc ASHP (Assure Mono 5/7/9/12/16)
| Does the heat pump stop? | Not stated |
|---|---|
| Engineer needed? | Yes |
The manual does not say whether the heat pump stops.
Resetting itself: unknown.
Manual reset: Power OFF/ON after correcting cause (ISM 13.4).
On the HP40 / Baxi Assure HP50 Monobloc ASHP
| Does the heat pump stop? | Not stated |
|---|---|
| Engineer needed? | Yes |
The manual does not say whether the heat pump stops.
Resetting itself: unknown.
Manual reset: Installer: correct cause then power OFF/ON (ISM 13.4).
On the HP60 / Baxi Assure HP55 High Temperature Monobloc ASHP (R290)
| Does the heat pump stop? | Not stated |
|---|---|
| Engineer needed? | Yes |
The manual does not say whether the heat pump stops.
Resetting itself: unknown.
Manual reset: unknown.
What you can check
- Note the exact code shown on the controller and when it appeared.
- Read the heating system pressure gauge and report the value to your installer (the manuals quote a minimum of about 1 bar cold).
- Check the filling loop is closed.
- In freezing weather do not leave the system switched off - the manuals warn water faults left unrepaired in winter can let the pump and pipes freeze.
- If the code persists or returns, contact a heat pump engineer.
What the engineer will check
On the Assure Monobloc ASHP (Assure Mono 5/7/9/12/16)
- Shut-off valves not fully open; filter needs cleaning; air in system; water pressure must be >1 bar (cold); pump speed; expansion vessel; circuit resistance too high.
Who to ask for: heating / heat pump engineer (hydraulics).
Certification: None beyond heating competence (MCS installer recommended).
On the HP40 / Baxi Assure HP50 Monobloc ASHP
- Shut-off valves not fully open; filter needs cleaning; air in system; water pressure must be >1 bar; pump speed; expansion vessel; circuit resistance too high for pump.
Who to ask for: heating / heat pump engineer (hydraulics).
Certification: None beyond heating competence (MCS installer recommended).
On the HP60 / Baxi Assure HP55 High Temperature Monobloc ASHP (R290)
- Diagnose per manufacturer service procedure (manual gives description only).
Who to ask for: heating / heat pump engineer (hydraulics).
Certification: None beyond heating competence (MCS installer recommended).
What you might notice
Sources
- Installation and owner's manual - Heat Pump air/water 'inverter' Assure Mono 5, 7, 9, 12, 16 ↗ · Back cover shows '7762758 - v05 - 19082020' (same number as the Assure Split manual - probably shared back-cover artwork) · page 75 · Reviewed 23 September 2026
- Installation and Service Manual - Heat Pump air/water 'inverter' HP40/50-4-1PHMB to HP40/50-13-3PHMB (United Kingdom) ↗ · 784570-01 (v1) · page 74 · Reviewed 23 September 2026
- Installation, user and service manual - Reversible monobloc air-to-water heat pump, outdoor unit HP60-4-1-PHMB to HP60-13-3-PHMB ↗ · 7888668 - v03 - 17072025 · page 60 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026