alpha innotec heat pump error codes

alpha innotec (ait-deutschland) · A niche brand in the UK. 99 codes across 1 product family, each taken from the manufacturer’s manuals. alpha innotec technical support ↗

Find a alpha innotec engineer →99 codes · reviewed 23 September 2026

Search within brand

Type the code on your display or a word from its meaning. Each code opens its own page with what it means, whether it is safe and what you can check.

99 codes

CodeMeaningStops?Homeowner check?
701
Error low pressure. Please call AS: Low-pressure pressostat or low-pressure sensor in the refrigerant circuit has responded (air/water), or for longer than 20 s (brine/water).
YesYes
702
Low pressure stop. Reset autom.: Air/water units only: low pressure in the refrigerant circuit has responded; heat pump restarts automatically after some time.
YesYes
703
Antifreeze. Please call installer: Air/water units only: heat pump running and flow temperature < 5 °C - frost danger detected.
YesYes
704
Error hot gas. Reset in hh:mm: Maximum hot-gas (discharge) temperature in the refrigerant circuit exceeded; automatic restart after the displayed time.
YesYes
705
Motor protection VEN. Please call installer: Air/water units only: fan motor protection has responded.
YesYes
706
Motor protection BCP. Please call installer: Brine/water or water/water units only: motor protection of the brine or well-water circulating pump or of the compressor has responded.
YesYes
707
Coding of HP. Please call installer: Break or short circuit of the coding bridge (coding resistor) in the heat pump after first switch-on.
YesYes
708
Return sensor. Please call installer: Break or short circuit in the return sensor.
YesYes
709
Flow sensor. Please call installer: Break or short circuit in the flow sensor. No fault shutdown for brine/water or water/water units.
PartlyYes
710
Hot gas sensor. Please call installer: Break or short circuit in the hot-gas sensor of the refrigerant circuit.
YesYes
711
External temp. sensor. Please call installer: Break or short circuit in the outdoor (external) temperature sensor. No fault shutdown; value fixed to -5 °C.
NoYes
712
Domestic hot water sensor. Please call installer: Break or short circuit in the domestic hot water sensor. No fault shutdown.
PartlyYes
713
HS-on sensor. Please call installer: Break or short circuit in the heat source sensor (inlet).
YesYes
714
Hot gas SW. Reset in hh:mm: Thermal application limit of the heat pump reached during DHW; domestic hot water off for hh:mm. Only triggers while compressor running.
PartlyYes
715
High-pressure switch-off. Reset autom.: High pressure in the refrigerant circuit has responded; automatic restart after some time.
YesYes
716
High-pressure fault. Please call installer: High-pressure pressostat in the refrigerant circuit has responded several times.
YesYes
717
Flow HS. Please call installer: Water/water units: flow switch has responded during pre-rinsing time or operation.
YesYes
718
Max. outside temp. Reset autom. in hh:mm: Air/water units only: outside temperature has exceeded permissible maximum; automatic restart after hh:mm.
YesYes
719
Min. outside temp. Reset autom. in hh:mm: Air/water units only: outside temperature has fallen below permissible minimum; automatic restart after hh:mm.
YesYes
720
HS temperature. Reset autom. in hh:mm: Brine/water or water/water units: temperature at evaporator outlet (heat source side) fell below the safety value several times; automatic restart after hh:mm.
YesYes
721
Low-pressure switch-off. Reset autom.: Low-pressure pressostat or sensor in the refrigerant circuit has responded; automatic restart after some time (brine/water and water/water).
YesYes
722
Tempdiff HW. Please call installer: Temperature spread in heating mode is negative (erroneous).
YesYes
723
Tempdiff SW. Please call installer: Temperature spread in domestic hot water mode is negative (erroneous).
YesYes
724
Tempdiff defrosting. Please call installer: Temperature spread in heating circuit > 15 K during defrosting (danger of frost).
YesYes
725
System error DHW. Please call installer: Domestic hot water fault: desired tank temperature substantially undershot.
PartlyYes
726
Sensor mixing circ 1. Please call installer: Break or short circuit in the mixing circuit 1 sensor.
PartlyYes
727
Brine pressure. Please call installer: Brine pressure pressostat responded during pre-rinsing time or operation.
YesYes
728
Sensor HS Off. Please call installer: Break or short circuit in the heat source sensor at the heat source outlet.
YesYes
729
Rotating field error. Please call installer: Compressor without power after switching on (rotating field / phase sequence).
YesYes
730
Screed heating error. Please call installer: Screed heating program could not reach a flow temperature level in the specified interval; program continues running.
NoYes
731
Timeout TDI: Temperature required for thermal disinfection could not be reached within the set switching times.
NoYes
732
Cooling fault. Please call installer: Heating water temperature of 16 °C undershot several times (cooling).
PartlyYes
733
Anode fault. Please call installer: Fault input of the impressed-current anode has responded.
PartlyYes
734
Anode fault. Please call installer: Error 733 present for more than two weeks; domestic hot water is locked.
PartlyYes
735
Error Ext. En. Please call installer: Only with expansion board: break or short circuit in the 'External energy source' sensor.
PartlyYes
736
Error solar collector. Please call installer: Only with expansion board: break or short circuit in the 'solar collector' sensor.
PartlyYes
737
Error solar tank. Please call installer: Only with expansion board: break or short circuit in the 'solar tank' sensor.
PartlyYes
738
Error mixing circle 2. Please call installer: Only with expansion board: break or short circuit in the 'mixing circle 2' sensor.
PartlyYes
739
Error mixing circle 3. Please call installer: Only with expansion board: break or short circuit in the 'mixing circle 3' sensor.
PartlyYes
750
Return sensor external. Please call installer: Break or short circuit in the external return sensor.
YesYes
751
Phase monitoring fault: Phase-sequence relay has responded.
YesYes
752
Flow error: Phase-sequence relay or flow switch has responded.
YesYes
755
Lost connection to slave. Please call installer: A slave (parallel/cascade mode) has not responded for more than 5 minutes.
PartlyYes
756
Lost connection to master. Please call installer: A master (parallel/cascade mode) has not responded for more than 5 minutes.
PartlyYes
757
Low-pressure fault in W/W-appliance: Low-pressure pressostat in a water/water unit triggered repeatedly or for more than 20 s. After three occurrences the installation can only be cleared by authorised service personnel.
YesYes
758
Defrosting malfunction: Five times in a row defrosting lasted longer than 10 minutes or ended with feed temperature < 10 °C.
YesYes
759
TDI message: Thermal disinfection could not be carried out correctly 5 times in succession.
NoYes
760
Defrosting fault: Defrosting ended 5 times in succession by maximum time (strong wind on evaporator).
YesYes
761
LIN timeout: LIN connection interrupted.
YesYes
762
Sensor compressor intake: Tü sensor error (compressor intake).
YesYes
763
Sensor evaporator intake: Tü1 sensor error (evaporator intake).
YesYes
764
Sensor compressor heater: Sensor error compressor heater.
YesYes
765
Suction gas Overheating (SSH): Suction gas superheat outside limits (above/below 2 K) for longer than 5 minutes. Auto reset after 5 minutes or manual; repeated occurrences permanently block the refrigerant circuit.
YesYes
766
compressor's functional range: Operation for 5 minutes outside the compressor's functional range; resets after max. 2 h.
YesYes
767
STB E-Rod: Safety temperature limiter (STB) of the electric heating element has been activated.
PartlyYes
768
Flow monitoring: Insufficient flow in defrost cycle.
YesYes
769
Pump control: No valid flow signal from the circulating pump. Reset autom.
YesYes
770
Low overheat: Superheat below limit value for a lengthy period.
YesYes
771
High overheat: Superheat outside limit value for a lengthy period (manual text reads 'below').
YesYes
775
SEC EVI valve: Electronic expansion valve in the EVI circuit no longer recognised by the control.
YesYes
776
limit of application-CP: Compressor operating outside its use limits for a lengthy period.
YesYes
777
Expansion valve: Electronic expansion valve is defective.
YesYes
778
Low pressure sensor: Low-pressure sensor is defective.
YesYes
779
High pressure sensor: High-pressure sensor is defective.
YesYes
780
EVI sensor: EVI sensor is defective.
YesYes
781
Liquid temp. sensor before EXV: Liquid temperature sensor upstream of the expansion valve is defective.
YesYes
782
Suction gas EVI temp. sensor: Suction gas EVI temperature sensor is defective.
YesYes
783
Communication SEC board - Inverter: Connection between SEC board and inverter is disrupted.
YesYes
784
VSS lockdown: Inverter is blocked.
YesYes
785
SEC-Board defective: Error found in the SEC board.
YesYes
786
Communication SEC board - Inverter: Connection between SEC board and HZ/IO is disrupted by the SEC board.
YesYes
787
VD alert: Compressor signals faults.
YesYes
788
Major VSS fault: Fault in the inverter.
YesYes
789
LIN/Encoding not found: Control unit unable to find coding: LIN connection interrupted or coding resistor not detected.
YesYes
790
Major VSS fault: Fault in the power supply of the inverter / compressor.
YesYes
791
ModBus connection lost Inverter: No ModBus communication with inverter for at least 10 s or 10 packets lost. Reset autom.
YesYes
792
LIN-connection lost: Unable to find a master board or any configuration.
YesYes
793
Inverter Temperature: Temperature sensor fault in the inverter / internal inverter temperature too high at least 5x within 24 h. Fault acknowledges itself.
YesYes
794
Overvoltage: Overvoltage on inverter.
YesYes
795
Undervoltage: Undervoltage on inverter.
YesYes
796
Safety switch off: Safety input triggered; manual reset required. Case 1 inverter malfunction; case 2 high-pressure pressostats triggered; case 3 (LWDV/Hybrox only) voltage fluctuations beyond standard.
YesYes
797
MLRH is not supported: Heating rod regulating is not supported.
NoYes
798
ModBus connection lost Fan: No ModBus communication with the fan for at least 10 s. Reset autom.
YesYes
799
ModBus connection lost ASB: No ModBus communication with the ASB board for at least 10 s. Reset autom.
YesYes
800
Desuperheater-error: Shutdown when desuperheater temperature >= 80 °C; released after 2 hours; if 5 times within 24 h error 800 is displayed.
YesYes
801
HP offline: The heating and heat pump controller has no internet connection.
NoYes
802
Temperature electrical switch box: Shutdown when switch-box temperature >= 80 °C; restarts below 70 °C. Reset autom.
YesYes
803
Temperature electrical switch box Blockage: Error 802 tripped 3 times within 24 hours; manual reset required.
YesYes
804
Sensor temperature electrical switch box: Sensor error: electrical switch box temperature.
Not statedYes
805
Sensor desuperheater: Sensor error: desuperheater temperature (or 'Enth' selected in FlexConfig - Out2 although not required).
Not statedYes
806
ModBus SEC: SEC board has no ModBus communication for at least 10 s or query failed 10 times in a row. Reset autom.
YesYes
807
Lost ModBus communication: All ModBus communication faults with unit components present simultaneously for at least 10 s. Reset autom.
YesYes
808
Hardware not supported: Controller software version incompatible with installed ASB hardware.
Not statedYes
809
Overheating hot gas (DSH): DSH_break triggered 3 times within 24 h. Reset autom. after 5 minutes or manually.
YesYes
810
version parallel mode: Controllers connected in parallel operation have different software versions.
PartlyYes
811
Check condensate pan. Please call installer: COPS float switch (condensate overflow protection) has tripped.
YesYes
812
Maximum flow rate. Please call installer: Maximum permissible flow rate of the circulation pump exceeded 5 times within 24 h.
Not statedYes
813
Inverter not compatible. Please call installer: The heat pump inverter is not compatible; compressor blocked, only operation with ZWE (additional heater) possible.
PartlyYes
814
Sensor defrosting. Please call installer: Defrosting sensor is defective.
Not statedYes