Does a PV array frame need earthing or bonding in the UK?
Short answer
Follow the IET PV Code of Practice decision tree in Section 5.13.2, Figure 5.7. MIS 3002 says correct use normally leads to protective or functional earthing of the array frame, and if the designer decides on neither, the justification must be recorded. Where a lightning protection system exists, design bonding or separation to BS EN 62305.
Last checked 24 September 2026 · 1 source
In more detail
- MIS 3002 cl.5.3.2.
- Earth continuity recorded on PV array test report where fitted.
- Class II modules/inverters reduce protective earthing needs but functional earthing may still apply.
The facts, dated
- 01MIS clause on array frame earthing justification — 5.3.2
standard · UK · checked 24 September 2026 · MCS