Why does my SolarEdge inverter keep switching off with 'AC voltage too high' on sunny days?
Short answer
Codes such as 2x1F, 2x21 or 18x1F mean the grid voltage measured at the inverter is above the UK limit it has been set to. On sunny middays, export can push local voltage up. The inverter reconnects by itself once voltage falls. If it happens often, the installer should check cable voltage rise and ask the DNO to investigate.
Last checked 24 September 2026 · 1 source
In more detail
- SolarEdge: verify country setting, check wire gauge, consult the grid operator.
- GB statutory supply voltage is 230 V +10%/-6%; protection settings must follow G98/G99.
- Never ask anyone to raise the protection limits without DNO agreement.
The facts, dated
- 01SolarEdge code 2x1F description — Grid voltage is above the country limit
manufacturer · UK · checked 24 September 2026 · knowledge-center.solaredge.com
What we saw in the field
Field evidence (installer videos) that DNOs cap export where local solar is saturated is consistent with high-voltage trips on busy LV feeders, but no video mentioned this specific code.