Solar · Error codes · GivEnergy
INV_PV_OVER_VOLTAGEGivEnergy · Cloud portal / GivEnergy app and Wi-Fi dongle

INV_PV_OVER_VOLTAGE on a GivEnergy Cloud portal / GivEnergy app and Wi-Fi dongle: PV over-voltage - check that the string voltage does not exceed 580 VDC

Short answer

On a GivEnergy inverter, INV_PV_OVER_VOLTAGE means: PV over-voltage - check that the string voltage does not exceed 580 VDC. The inverter stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 24 September 2026 · 1 source

What it means

The manual says: PV over-voltage - check that the string voltage does not exceed 580 VDC.

Part involved: PV input over-voltage.

Likely causes:

  • PV over-voltage.

Is it safe?

Switch the inverter off at its isolator and call an engineer.

Does the inverter stop?Yes
SeveritySafety lockout
Engineer needed?Yes

The inverter stops until the fault clears or is reset.

Resetting itself: no.

Manual reset: yes, after string design is corrected.

What you can check

  • Read and note the exact code and time from the inverter display or app (screenshot).
  • Call the installer. Do not touch DC cabling.
  • GivEnergy's customer guide allows a restart: turn off the DC (solar) and AC isolators, then restart the battery with its side button; or use the app/portal. Contact the installer if the alarm returns.

What the engineer will check

  • Measure open-circuit string voltage (cold-weather Voc rise).
  • Check string design against inverter max DC voltage.
  • Check for mixed/incorrect module counts.

Who to ask for: PV installer / system designer.

Certification: Electrician competent in grid-connected PV (BS 7671 Section 712; IET Code of Practice for Grid-connected Solar PV), ideally the original MCS-certified PV installer; brand-approved/trained installer to keep manufacturer warranty.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 24 September 2026