AL09MasterTherm

AL09 on a MasterTherm heat pump: Flow - insufficient or no flow of water through heat pump

Short answer

On a MasterTherm heat pump, AL09 means: Flow - insufficient or no flow of water through heat pump. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 1 source

What it means

On the pCO5/pGD controller alarms - air/water units (BoxAir, BoxAir Inverter, BoxAir Inverter P, AirMaster, EasyMaster)

The manual says: Flow - insufficient or no flow of water through heat pump.

Part involved: flow switch / circulation pump / water filter.

When it shows: Control action: Switches off compressor and fan. Operator guidance: Check and clean the heating water filter; contact installer if repeated.

Likely causes:

  • Circulation pump error.
  • Clogged heating water filter.

On the pCO5/pGD controller alarms - brine/water and water/water units (AquaMaster, AquaMaster Inverter, Inverter P, Combi)

The manual says: Flow - low cooling/heating water flow.

Part involved: flow switch / circulator / strainer.

When it shows: Control action: Switches off compressor and brine circulator. Operator guidance: Switch unit off, check water strainer; repeated - call service.

Likely causes:

  • Circulator malfunction.
  • Full cooling/heating water strainer.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Resets automatically after the minimum compressor off time (~6 min) if the same alarm occurs fewer than 3 times per compressor operating hour.

Manual reset: After 3 occurrences in 1 compressor operating hour the unit is blocked (ALARM key lit steadily); manual reset by pressing ALARM key on the alarm display (pGD) or RESET on pGDx Alarm Management.

What you can check

On the pCO5/pGD controller alarms - air/water units (BoxAir, BoxAir Inverter, BoxAir Inverter P, AirMaster, EasyMaster)

  • Read and note the alarm (ALx code/text) and the alarm counter shown on the pGD/pGDx display.
  • Check the heat pump breaker/isolator in the consumer unit is on.
  • Check the heating system pressure gauge reading.
  • Check that radiator/zone valves you normally operate are open.

On the pCO5/pGD controller alarms - brine/water and water/water units (AquaMaster, AquaMaster Inverter, Inverter P, Combi)

  • Read and note the alarm (ALx code/text) and the alarm counter shown on the pGD/pGDx display.
  • Check the heat pump breaker/isolator in the consumer unit is on.
  • Check the heating system pressure gauge reading.

What the engineer will check

On the pCO5/pGD controller alarms - air/water units (BoxAir, BoxAir Inverter, BoxAir Inverter P, AirMaster, EasyMaster)

  • Clean heating water filter/strainer.
  • Check circulation pump and flow switch.
  • Vent system.

Who to ask for: heat pump service engineer (refrigeration/controls).

Certification: F-gas certification (refrigerant circuit work); electrical competence for switchboard work.

On the pCO5/pGD controller alarms - brine/water and water/water units (AquaMaster, AquaMaster Inverter, Inverter P, Combi)

  • Clean water strainer, check circulator and flow switch.

Who to ask for: ground source heat pump engineer (refrigeration/controls).

Certification: F-gas certification (refrigerant circuit work); electrical competence for switchboard work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026