AL03MasterTherm

AL03 on a MasterTherm heat pump: High Discharge Temperature - high compressor discharge gas temperature

Short answer

On a MasterTherm heat pump, AL03 means: High Discharge Temperature - high compressor discharge gas temperature. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 1 source

What it means

On the pCO5/pGD controller alarms - air/water units (BoxAir, BoxAir Inverter, BoxAir Inverter P, AirMaster, EasyMaster)

The manual says: High Discharge Temperature - high compressor discharge gas temperature.

Part involved: compressor discharge temperature probe.

When it shows: Control action: Switches off compressor and fan. Operator guidance: Reduce requested heating water temperature, check bleeding/filling, clean heating water filter; report if repeated.

Likely causes:

  • Insufficient refrigerant charge or minor leak.
  • High heating water temperature.
  • Extremely low outdoor air temperature.
  • Sensor failure (see AL10).

On the pCO5/pGD controller alarms - brine/water and water/water units (AquaMaster, AquaMaster Inverter, Inverter P, Combi)

The manual says: High Discharge Temperature.

Part involved: compressor discharge probe.

When it shows: Control action: Switches off compressor and brine circulator. Operator guidance: Decrease water temperature, check deaeration/filling, clean strainer; repeated - call service.

Likely causes:

  • Too high water temperature.
  • Full water strainer.
  • Water circulator malfunction.
  • Slight refrigerant leak.
  • Temperature probe problem (AL10).

Is it safe?

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Resets automatically after the minimum compressor off time (~6 min) if the same alarm occurs fewer than 3 times per compressor operating hour.

Manual reset: After 3 occurrences in 1 compressor operating hour the unit is blocked (ALARM key lit steadily); manual reset by pressing ALARM key on the alarm display (pGD) or RESET on pGDx Alarm Management.

What you can check

On the pCO5/pGD controller alarms - air/water units (BoxAir, BoxAir Inverter, BoxAir Inverter P, AirMaster, EasyMaster)

  • Read and note the alarm (ALx code/text) and the alarm counter shown on the pGD/pGDx display.
  • Check the heat pump breaker/isolator in the consumer unit is on.
  • Reduce the requested heating water temperature on the controller.
  • Check the heating system pressure gauge reading.

On the pCO5/pGD controller alarms - brine/water and water/water units (AquaMaster, AquaMaster Inverter, Inverter P, Combi)

  • Read and note the alarm (ALx code/text) and the alarm counter shown on the pGD/pGDx display.
  • Check the heat pump breaker/isolator in the consumer unit is on.
  • Reduce the requested heating water temperature.
  • Check the heating system pressure gauge reading.

What the engineer will check

On the pCO5/pGD controller alarms - air/water units (BoxAir, BoxAir Inverter, BoxAir Inverter P, AirMaster, EasyMaster)

  • Leak test and check refrigerant charge.
  • Check discharge probe (AL10).
  • Clean heating water filter, vent system.

Who to ask for: heat pump service engineer (refrigeration/controls).

Certification: F-gas certification (refrigerant circuit work); electrical competence for switchboard work.

On the pCO5/pGD controller alarms - brine/water and water/water units (AquaMaster, AquaMaster Inverter, Inverter P, Combi)

  • Leak test/charge check.
  • Probe check.
  • Clean strainer.

Who to ask for: ground source heat pump engineer (refrigeration/controls).

Certification: F-gas certification (refrigerant circuit work); electrical competence for switchboard work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026