SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · MasterTherm
AL01MasterTherm

AL01 on a MasterTherm heat pump: Low Pressure - compressor low suction pressure

Short answer

On a MasterTherm heat pump, AL01 means: Low Pressure - compressor low suction pressure. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 1 source

What it means

On the pCO5/pGD controller alarms - air/water units (BoxAir, BoxAir Inverter, BoxAir Inverter P, AirMaster, EasyMaster)

The manual says: Low Pressure - compressor low suction pressure.

Part involved: low pressure transducer / evaporator.

When it shows: Control action: Switches off compressor and fan. Operator guidance: Wait for the condition to end; if evaporator iced, perform a manual defrost once the unit restarts; contact installer if repeated.

Likely causes:

  • Extremely low outdoor air temperature (below -20 C).
  • Freezing (icing) of the evaporator.
  • Fan operating failure.

On the pCO5/pGD controller alarms - brine/water and water/water units (AquaMaster, AquaMaster Inverter, Inverter P, Combi)

The manual says: Low pressure - compressor low suction pressure.

Part involved: evaporator / brine circuit.

When it shows: Control action: Switches off compressor and brine circulator. Operator guidance: Switch off unit, clean closed-loop strainer, check brine pressure; repeated problem - call service.

Likely causes:

  • Low closed-loop (brine) temperature.
  • Evaporator freezing.
  • Brine circulator malfunction.
  • Full (clogged) closed-loop strainer.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Resets automatically after the minimum compressor off time (~6 min) if the same alarm occurs fewer than 3 times per compressor operating hour.

Manual reset: After 3 occurrences in 1 compressor operating hour the unit is blocked (ALARM key lit steadily); manual reset by pressing ALARM key on the alarm display (pGD) or RESET on pGDx Alarm Management.

What you can check

On the pCO5/pGD controller alarms - air/water units (BoxAir, BoxAir Inverter, BoxAir Inverter P, AirMaster, EasyMaster)

  • Read and note the alarm (ALx code/text) and the alarm counter shown on the pGD/pGDx display.
  • Check the heat pump breaker/isolator in the consumer unit is on.
  • If heavy icing and the manual permits, start a manual defrost from the pGD display (UP+DOWN together) or Defrost Info screen.
  • Check the outdoor unit is not blocked by snow, ice, leaves or debris.

On the pCO5/pGD controller alarms - brine/water and water/water units (AquaMaster, AquaMaster Inverter, Inverter P, Combi)

  • Read and note the alarm (ALx code/text) and the alarm counter shown on the pGD/pGDx display.
  • Check the heat pump breaker/isolator in the consumer unit is on.

What the engineer will check

On the pCO5/pGD controller alarms - air/water units (BoxAir, BoxAir Inverter, BoxAir Inverter P, AirMaster, EasyMaster)

  • Check fan motor and fan circuit.
  • Check refrigerant charge/leaks and EEV operation.
  • Check low-pressure alarm setpoint (A76) and delay (I18).

Who to ask for: heat pump service engineer (refrigeration/controls).

Certification: F-gas certification (refrigerant circuit work); electrical competence for switchboard work.

On the pCO5/pGD controller alarms - brine/water and water/water units (AquaMaster, AquaMaster Inverter, Inverter P, Combi)

  • Clean closed-loop strainer.
  • Check brine pressure/antifreeze concentration.
  • Check brine pump.

Who to ask for: ground source heat pump engineer (refrigeration/controls).

Certification: F-gas certification (refrigerant circuit work); electrical competence for switchboard work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026