SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Worcester Bosch
A01-811Worcester Bosch · Worcester Bosch, all models

A01-811 on a Worcester Bosch heat pump: DHW provision: thermal disinfection unsuccessful

Short answer

On a Worcester Bosch heat pump, A01-811 means: DHW provision: thermal disinfection unsuccessful. The heat pump keeps running. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: DHW provision: thermal disinfection unsuccessful.

Part involved: thermal disinfection / DHW sensor.

When it shows: DHW provision: thermal disinfection unsuccessful.

Likely causes:

  • Constant DHW draw-off (leak/taps open); DHW sensor mispositioned; DHW priority deselected so output insufficient; cylinder coil not vented; incorrect boiler/cylinder pipework; cylinder primary pump undersized; excessive DHW circulation losses; faulty DHW sensor; booster heater too small for volume (increase maximum duration 60-240 min).

Is it safe?

Does the heat pump stop?No
SeverityWarning
Engineer needed?Yes

The heat pump keeps running.

Resetting itself: Clears when cause is removed.

Manual reset: User guides (7001i/7400i AWE, 3400i AWS, section 3.5): user may confirm the fault by pressing the selector; if it persists call the contractor with fault code, sub-code and user-interface ID no.

What you can check

  • Read and note the full code (and sub-code) shown on the controller and pass it to your installer.
  • Check no hot tap is left running and there is no visible hot-water leak.
  • Confirm/acknowledge the fault once at the controller (press selector) as the user guide allows; if it returns, call the installer.

What the engineer will check

  • Check sensor position/resistance, coil venting, primary pump capacity, circulation losses, DHW max duration setting.

Who to ask for: heat pump installer / heating engineer.

Certification: None specific for hydraulic checks; MCS-certified installer recommended for system changes.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026