F.981 on a Viessmann One Base: Minimum flow rate for DHW undershot

Short answer

On a Viessmann heat pump, F.981 means: Minimum flow rate for DHW undershot. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Minimum flow rate for DHW undershot.

Part involved: Minimum flow rate for DHW undershot.

When it shows: System characteristics: No DHW heating.

Likely causes:

  • The flow rate falls below the minimum flow rate during DHW heating.

Is it safe?

Does the heat pump stop?Partly
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: Not stated per code in Viessmann document 6199961 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
  • Check the system pressure shown on the HMI "System overview" (6249162 p.35) or pressure gauge and report a low reading; make sure the filling loop is closed.

What the engineer will check

  • Isolate the system from the power supply. Wait at least 2 min. Switch on the system.
  • Loading cylinder individually: If necessary, open closed shut-off valves and 3-way valves in the direction of DHW heating.
  • Restart the venting function via ViGuide.
  • Indoor unit individually: Check the quick-action air vent valve:.
  • Quick-action air vent valve must be permanently open.
  • Check for leaks. Replace the quick-action air vent valve if necessary.
  • Extension unit individually: Check the system pressure at the pressure gauge or via ViGuide. Top up with water if necessary.
  • Indoor unit individually: Check the cylinder loading pump. Replace if necessary.

Who to ask for: Viessmann-trained heat pump installer/service engineer.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026