Heat pumps · Error codes · Viessmann
A.16Viessmann · One Base

A.16 on a Viessmann One Base: Insufficient flow rate

Short answer

On a Viessmann heat pump, A.16 means: Insufficient flow rate. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Insufficient flow rate.

Part involved: Insufficient flow rate.

When it shows: System characteristics:; Refrigerant circuit off: Inverter and compressor cannot be switched on.; Instantaneous heating water heater is switched off. The instantaneous heating water heater will not start.

Likely causes:

  • Minimum flow rate undershot.

Is it safe?

Does the heat pump stop?Yes
SeverityWarning
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
  • Check the system pressure shown on the HMI "System overview" (6249162 p.35) or pressure gauge and report a low reading; make sure the filling loop is closed.

What the engineer will check

  • Open shut-off valves in the direction of flow. Remove any blockages.
  • Clean the heating water filter. Clean the dirt separator if necessary.
  • Check the integral secondary pump/heating circuit pump in heating/cooling circuit.
  • Check the impeller. Remove the rotor if necessary. Remove dirt. Flush the system if necessary.
  • Check connection of flow sensor (if installed) at X19.1 to X19.4 on the EHCU electronics module:.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.

Who to ask for: Viessmann-trained heat pump installer/service engineer.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.