F.876 on a Viessmann One Base: Lead break, combined sensor, flow rate/temperature

Short answer

On a Viessmann heat pump, F.876 means: Lead break, combined sensor, flow rate/temperature. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Lead break, combined sensor, flow rate/temperature.

Part involved: Lead break, combined sensor, flow rate/temperature.

When it shows: System characteristics: Heat pump off.

Likely causes:

  • Only for heat pumps with integral flow sensor: Lead break, flow sensor.

Is it safe?

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
  • Check the system pressure shown on the HMI "System overview" (6249162 p.35) or pressure gauge and report a low reading; make sure the filling loop is closed.

What the engineer will check

  • Only for heat pumps with integral flow sensor:.
  • Check flow sensor and connections X19.1 to X19.4 on the EHCU electronics module:.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
  • Check voltage U between X19.2 and X19.4 on EHCU electronics module:.
  • U = 5 V : Replace flow sensor.
  • No voltage: Replace EHCU electronics module.

Who to ask for: Viessmann-trained heat pump installer/service engineer.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.