F.834 on a Viessmann One Base: Inverter phase fault on mains side
Short answer
On a Viessmann heat pump, F.834 means: Inverter phase fault on mains side. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Inverter phase fault on mains side.
Part involved: Inverter phase fault on mains side.
When it shows: System characteristics: Refrigerant circuit off: Inverter and compressor cannot be switched on.
Likely causes:
- Power supply on inverter faulty.
Is it safe?
| Does the heat pump stop? | Yes |
|---|---|
| Engineer needed? | Yes |
The heat pump stops until the fault clears or is reset.
Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).
Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.
What you can check
- On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
- Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
- Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
What the engineer will check
- Check the surge protection device in the meter box or on the outdoor unit. Switch on if necessary.
- Check all connections to the inverter:.
- Check wires and plugs for correct seating.
- Check connections for contact corrosion.
- Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. Replace cable if necessary.
- Check the phase connections on the inverter for a clockwise rotating field.
- Check whether there is a fault in the power grid caused by the power supply utility.
- Only Vitocal 250-A.../252-A, sizes 16 to 19: Check the fuses on plug X6 on the inverter (IPE). Replace inverter if necessary.
Who to ask for: Viessmann-trained heat pump engineer / qualified electrician.
Certification: Qualified electrician for work on electrical equipment (Viessmann safety instructions).
What you might notice
Sources
- Service instructions for contractors: Heat pumps in monoblock design incl. hybrid – System configuration and diagnostics (Vitocal 150-A/151-A/250-A/252-A, IDU-A, AWMOF-151/251, AquaSnap 30AWH, BI-BLOC R290) (6199893 GB 01/2026) ↗ · 6199893 GB 01/2026 (VSA00009) · page 148-149 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026