F.812 on a Viessmann One Base: Fault, upper fan
Short answer
On a Viessmann heat pump, F.812 means: Fault, upper fan. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Fault, upper fan.
Part involved: Fault, upper fan.
When it shows: System characteristics: The refrigerant circuit will not start.
Likely causes:
- Upper fan not running.
Is it safe?
| Does the heat pump stop? | Not stated |
|---|---|
| Engineer needed? | Yes |
The manual does not say whether the heat pump stops.
Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).
Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.
What you can check
- On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
- Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
- Check the outdoor unit is not blocked by leaves, debris or snow.
What the engineer will check
- Check the location of the outdoor unit for vulnerability to wind. If required, take steps to protect from wind, e.g. with an air diverter in ….
- Isolate the outdoor unit from the power supply.
- Check fan and fan motor bearings for damage and blockages: Turn slowly by hand. Remove any blockages. Replace fan motor if required.
- Check 6.3 A fuse at X2 (L2) of VCMU refrigerant circuit controller. Replace fuse if required.
- If the fan does not start automatically, check connection X18 on the VCMU refrigerant circuit controller:.
- Check wires and plugs for correct seating.
- Check connections for contact corrosion.
- Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.
Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).
What you might notice
Sources
- Service instructions for contractors: Heat pumps in monoblock design incl. hybrid – System configuration and diagnostics (Vitocal 150-A/151-A/250-A/252-A, IDU-A, AWMOF-151/251, AquaSnap 30AWH, BI-BLOC R290) (6199893 GB 01/2026) ↗ · 6199893 GB 01/2026 (VSA00009) · page 147 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026