F.812 on a Viessmann One Base: Fault, upper fan

Short answer

On a Viessmann heat pump, F.812 means: Fault, upper fan. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Fault, upper fan.

Part involved: Fault, upper fan.

When it shows: System characteristics: The refrigerant circuit will not start.

Likely causes:

  • Upper fan not running.

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the outdoor unit is not blocked by leaves, debris or snow.

What the engineer will check

  • Check the location of the outdoor unit for vulnerability to wind. If required, take steps to protect from wind, e.g. with an air diverter in ….
  • Isolate the outdoor unit from the power supply.
  • Check fan and fan motor bearings for damage and blockages: Turn slowly by hand. Remove any blockages. Replace fan motor if required.
  • Check 6.3 A fuse at X2 (L2) of VCMU refrigerant circuit controller. Replace fuse if required.
  • If the fan does not start automatically, check connection X18 on the VCMU refrigerant circuit controller:.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.

Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.

Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.