F.793Viessmann · One Base

F.793 on a Viessmann One Base: Failure, instantaneous heating water heater, phase 3

Short answer

On a Viessmann heat pump, F.793 means: Failure, instantaneous heating water heater, phase 3. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Failure, instantaneous heating water heater, phase 3.

Part involved: Failure, instantaneous heating water heater, phase 3.

When it shows: System characteristics: Phase 3 of the instantaneous heating water heater not available.

Likely causes:

  • No power supply to phase 3 of the instantaneous heating water heater.

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).

What the engineer will check

  • Turn off the ON/OFF switch on the indoor unit. Wait at least 2 min. Turn on the ON/OFF switch.
  • Check the following connections:.
  • Wall mounted indoor unit: 230 V~ junction box, terminals 136.1 to 136.N3 Floorstanding indoor unit: Terminal area 230 V~/400 V~, terminals 136.L1 to 136.N3.
  • Relay K3 on EHCU electronics module.
  • High limit safety cut-out.
  • Instantaneous heating water heater.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.

Who to ask for: Viessmann-trained heat pump engineer / qualified electrician.

Certification: Qualified electrician for work on electrical equipment (Viessmann safety instructions).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026