F.765 on a Viessmann One Base: Communication error with another CAN bus subscriber

Short answer

On a Viessmann heat pump, F.765 means: Communication error with another CAN bus subscriber. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Communication error with another CAN bus subscriber.

Part involved: Communication error with another CAN bus subscriber.

When it shows: System characteristics:; Heating/cooling capacity and/or DHW output impaired; No mechanical ventilation; No use of self-generated power via power storage unit.

Likely causes:

  • Communication error with another CAN bus subscriber (e.g. lag heat pump or other appliance).

Is it safe?

Does the heat pump stop?Partly
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).

What the engineer will check

  • Check the following CAN bus connections:.
  • Connections X8.1 to X8.3 on plug 91 on the HPMU electronics module.
  • Wall mounted indoor unit: Connection on device underside, 6-pole connection socket on the left, terminals 1.CAN L to 3.CAN H Floorstanding indoor unit: Terminal area ….
  • Check connection to other CAN bus subscribers.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
  • Check CAN L/CAN H assignment.

Who to ask for: Viessmann-trained heat pump installer/service engineer.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026