F.685 on a Viessmann One Base: Communication error, HPMU electronics module

Short answer

On a Viessmann heat pump, F.685 means: Communication error, HPMU electronics module. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Communication error, HPMU electronics module.

Part involved: Communication error, HPMU electronics module.

When it shows: System characteristics:; Function of connected components in emergency mode; Frost protection enabled; Passive frost protection on EHCU electronics module.

Likely causes:

  • HPMU electronics module communication error.

Is it safe?

Does the heat pump stop?Partly
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: Not stated per code in Viessmann document 6199961 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).

What the engineer will check

  • Isolate the system from the power supply. Wait at least 2 min. Switch on the system.
  • Check the CAN bus connection between the indoor unit and outdoor unit (CAN bus communication cable):.
  • Wall mounted indoor unit: Connection on the underside of the appliance, 5pin connection socket on the right, terminals 72.L to 72.H.
  • Indoor unit with integral DHW cylinder/loading cylinder: Terminal area for extra low voltage (ELV) < 42 V, luster terminal for bus connections, terminals 72.3 to ….
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
  • Shielding must be connected to CAN Ground (GND).

Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.

Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).