F.548 on a Viessmann One Base: Lead break, flow temperature sensor, heating/cooling circuit 4
Short answer
On a Viessmann heat pump, F.548 means: Lead break, flow temperature sensor, heating/cooling circuit 4. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Lead break, flow temperature sensor, heating/cooling circuit 4.
Part involved: Lead break, flow temperature sensor, heating/cooling circuit 4.
When it shows: System characteristics: Mixer closes. Heating circuit pump is operational.
Likely causes:
- Lead break, flow temperature sensor, heating/cooling circuit 4 with mixer.
- Incorrect configuration during commissioning.
Is it safe?
| Does the heat pump stop? | Not stated |
|---|---|
| Engineer needed? | Yes |
The manual does not say whether the heat pump stops.
Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).
Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.
What you can check
- On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
- Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
- Check the operating program, time program and room temperature settings on the HMI.
What the engineer will check
- Check configuration. Adjust settings if required.
- Check setting of rotary switch S1 on ADIO electronics module (EM-MX extension): See chapter "Rotary switch S1 on electronics modules".
- Check connection TS1.1/TS1.2 on the ADIO electronics module:.
- Check wires and plugs for correct seating.
- Check connections for contact corrosion.
- Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
- Check resistor R for NTC 10 kΩ on the disconnected plug. If R > 300 kΩ, replace the sensor.
- Replace the ADIO electronics module.
Who to ask for: Viessmann-trained heat pump installer/service engineer.
What you might notice
Sources
- Service instructions for contractors: Heat pumps in monoblock design incl. hybrid – System configuration and diagnostics (Vitocal 150-A/151-A/250-A/252-A, IDU-A, AWMOF-151/251, AquaSnap 30AWH, BI-BLOC R290) (6199893 GB 01/2026) ↗ · 6199893 GB 01/2026 (VSA00009) · page 135 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026