F.34 on a Viessmann One Base: Short circuit, primary inlet temperature sensor, heat pump
Short answer
On a Viessmann heat pump, F.34 means: Short circuit, primary inlet temperature sensor, heat pump. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Short circuit, primary inlet temperature sensor, heat pump.
Part involved: Short circuit, primary inlet temperature sensor, heat pump.
When it shows: System characteristics: Refrigerant circuit off.
Likely causes:
- Short circuit, air inlet temperature sensor.
Is it safe?
| Does the heat pump stop? | Yes |
|---|---|
| Engineer needed? | Yes |
The heat pump stops until the fault clears or is reset.
Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).
Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.
What you can check
- On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
- Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
- Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
What the engineer will check
- Check the sensor and connection X16.3/X16.4 on the VCMU refrigerant circuit controller:.
- Check wires and plugs for correct seating.
- Check connections for contact corrosion.
- Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
- Check resistor R for NTC 10 kΩ on the disconnected plug. If R < 500 Ω, replace the sensor.
- Replace VCMU refrigerant circuit controller.
Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.
Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).
What you might notice
Sources
- Service instructions for contractors: Heat pumps in monoblock design incl. hybrid – System configuration and diagnostics (Vitocal 150-A/151-A/250-A/252-A, IDU-A, AWMOF-151/251, AquaSnap 30AWH, BI-BLOC R290) (6199893 GB 01/2026) ↗ · 6199893 GB 01/2026 (VSA00009) · page 123 · Reviewed 23 September 2026