F.27 on a Viessmann One Base: Lead break, top buffer temperature sensor

Short answer

On a Viessmann heat pump, F.27 means: Lead break, top buffer temperature sensor. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Lead break, top buffer temperature sensor.

Part involved: Lead break, top buffer temperature sensor.

When it shows: System characteristics: Buffer heating not possible.

Likely causes:

  • Lead break, top buffer temperature sensor.

Is it safe?

Does the heat pump stop?Partly
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).

What the engineer will check

  • Check the sensor at the following connections:.
  • Terminals X17.1/X17.2 on the EHCU electronics module.
  • Wall mounted indoor unit: Connection on underside of appliance, 6-pin connection socket on the left, terminals 5 and 6.
  • Floorstanding indoor unit: Terminal area for extra low voltage (ELV) < 42 V, luster terminal for sensors, terminals 7 and 8.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
  • Check resistor R for NTC 10 kΩ on the disconnected plug. If R > 300 kΩ, replace the sensor.

Who to ask for: Viessmann-trained heat pump installer/service engineer.

Sources

A code explains what the controller detected, not a confirmed root cause.