F.1225 on a Viessmann One Base: Required oil sump temperature not reached

Short answer

On a Viessmann heat pump, F.1225 means: Required oil sump temperature not reached. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Required oil sump temperature not reached.

Part involved: Required oil sump temperature not reached.

When it shows: System characteristics:; Heat pump does not start.; Compressor off.

Likely causes:

  • Oil sump temperature sensor faulty or incorrectly installed.
  • Oil sump heater faulty or incorrectly installed.

Is it safe?

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).

What the engineer will check

  • Check oil sump temperature sensor:.
  • Check connection X20.3/X20.4 on the VCMU refrigerant circuit controller:.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
  • Check resistor R for NTC 10 kΩ on the disconnected plug:.
  • Lead break: If R > 300 kΩ, replace the sensor.
  • Short circuit: If R < 500 Ω, replace the sensor.

Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.

Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.