F.1213 on a Viessmann One Base: Communication error, refrigerant circuit controller, outdoor unit 2

Short answer

On a Viessmann heat pump, F.1213 means: Communication error, refrigerant circuit controller, outdoor unit 2. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Communication error, refrigerant circuit controller, outdoor unit 2.

Part involved: Communication error, refrigerant circuit controller, outdoor unit 2.

When it shows: System characteristics: The refrigerant circuit will not start.

Likely causes:

  • Communication fault with the VCMU refrigerant circuit controller of outdoor unit 2.

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.

What the engineer will check

  • Check power supply of outdoor unit. Switch on if necessary.
  • Check the CAN bus connection between outdoor unit 1 and outdoor unit 2:.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
  • Shielding must be connected to CAN Ground (GND).
  • Check cable type: Li2YCYv, twisted pair, shielded or 2-core CAT5, shielded.
  • Check cable length.

Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.

Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026