F.1194 on a Viessmann One Base: Inverter overcurrent, internal power module

Short answer

On a Viessmann heat pump, F.1194 means: Inverter overcurrent, internal power module. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Inverter overcurrent, internal power module.

Part involved: Inverter overcurrent, internal power module.

When it shows: System characteristics:; Output demand to heat pump not possible; Compressor not available.

Likely causes:

  • Max. permissible load current for the inverter was exceeded.

Is it safe?

Does the heat pump stop?Partly
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).

What the engineer will check

  • Isolate the outdoor unit from the power supply. Wait at least 2 min. Switch on voltage again.
  • Check connections U, V, W on the inverter:.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. Replace cable if necessary.
  • Check connections X12 to X14 on the compressor for short circuit with the cable disconnected. Replace compressor if required.
  • Replace inverter.

Who to ask for: Viessmann-trained heat pump engineer / qualified electrician.

Certification: Qualified electrician for work on electrical equipment (Viessmann safety instructions).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.