F.1191 on a Viessmann One Base: Fault, sensor interlock input 1

Short answer

On a Viessmann heat pump, F.1191 means: Fault, sensor interlock input 1. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Fault, sensor interlock input 1.

Part involved: Fault, sensor interlock input 1.

When it shows: System characteristics:; Output demand to heat pump not possible; Compressor not available.

Likely causes:

  • Internal fault in inverter safety circuit.
  • Faulty connection at input for inverter safety circuit.
  • External protection equipment has responded, e.g. RCDs, lightning protection, etc.

Is it safe?

Does the heat pump stop?Partly
SeveritySafety lockout
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: Measures include resetting/unlocking the refrigerant circuit via HMI service menu "Reset outdoor unit" or ViGuide (engineer, password-protected; 6199893 p.118).

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).

What the engineer will check

  • Check connection X1.3/X1.4 (STO1) on the inverter:.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
  • Check the function of the high pressure switch PSH.
  • Isolate the outdoor unit from the power supply. Wait at least 2 min. Switch on voltage again.
  • Replace inverter.
  • Unlock refrigerant circuit.

Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.

Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026