F.1035 on a Viessmann One Base: Communication fault, internal CAN bus
Short answer
On a Viessmann heat pump, F.1035 means: Communication fault, internal CAN bus. The heat pump keeps running. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Communication fault, internal CAN bus.
Part involved: Communication fault, internal CAN bus.
When it shows: System characteristics: Limited normal operation.
Likely causes:
- Short circuit or lead break, internal CAN bus.
- Connections 72.CAN L/72.CAN H interchanged.
Is it safe?
| Does the heat pump stop? | No |
|---|---|
| Engineer needed? | Yes |
The heat pump keeps running.
Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).
Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.
What you can check
- On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
- Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
What the engineer will check
- Only Vitocal 250-A.../252-A, sizes 16 to 19:.
- Isolate the system from the power supply. Wait at least 2 min. Switch on the system.
- Check the CAN bus connection between the indoor unit and outdoor unit:.
- Wall mounted indoor unit: Connection on underside of appliance, 5-pin connection socket on the right, terminals 72.L to 72.H Floorstanding indoor unit: Terminal area for ….
- Connection between X10.1 to X10.5 on the EHCU electronics module and X4.1 to X4.5 on the HPMU electronics module.
- Connecting cable between the HPMU electronics module at connection X5 and the HMI programming unit.
- Connection between X7.1 to X7.3 on the VCMU refrigerant circuit controller and X5.1 to X5.3 on the EHCU electronics module.
- Connection between X11.1 to X11.3 on the VCMU refrigerant circuit controller and IPS_X5:1 to IPS_X5:3 on the inverter.
Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.
Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).
Sources
- Service instructions for contractors: Heat pumps in monoblock design incl. hybrid – System configuration and diagnostics (Vitocal 150-A/151-A/250-A/252-A, IDU-A, AWMOF-151/251, AquaSnap 30AWH, BI-BLOC R290) (6199893 GB 01/2026) ↗ · 6199893 GB 01/2026 (VSA00009) · page 179-180 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026