F.1035 on a Viessmann One Base: Communication fault, internal CAN bus

Short answer

On a Viessmann heat pump, F.1035 means: Communication fault, internal CAN bus. The heat pump keeps running. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Communication fault, internal CAN bus.

Part involved: Communication fault, internal CAN bus.

When it shows: System characteristics: Limited normal operation.

Likely causes:

  • Short circuit or lead break, internal CAN bus.
  • Connections 72.CAN L/72.CAN H interchanged.

Is it safe?

Does the heat pump stop?No
Engineer needed?Yes

The heat pump keeps running.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.

What the engineer will check

  • Only Vitocal 250-A.../252-A, sizes 16 to 19:.
  • Isolate the system from the power supply. Wait at least 2 min. Switch on the system.
  • Check the CAN bus connection between the indoor unit and outdoor unit:.
  • Wall mounted indoor unit: Connection on underside of appliance, 5-pin connection socket on the right, terminals 72.L to 72.H Floorstanding indoor unit: Terminal area for ….
  • Connection between X10.1 to X10.5 on the EHCU electronics module and X4.1 to X4.5 on the HPMU electronics module.
  • Connecting cable between the HPMU electronics module at connection X5 and the HMI programming unit.
  • Connection between X7.1 to X7.3 on the VCMU refrigerant circuit controller and X5.1 to X5.3 on the EHCU electronics module.
  • Connection between X11.1 to X11.3 on the VCMU refrigerant circuit controller and IPS_X5:1 to IPS_X5:3 on the inverter.

Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.

Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).

Sources

A code explains what the controller detected, not a confirmed root cause.