F.1011 on a Viessmann One Base: Fault, high pressure sensor, refrigerant circuit
Short answer
On a Viessmann heat pump, F.1011 means: Fault, high pressure sensor, refrigerant circuit. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Fault, high pressure sensor, refrigerant circuit.
Part involved: Fault, high pressure sensor, refrigerant circuit.
When it shows: System characteristics: Refrigerant circuit off.
Likely causes:
- Fault, high pressure sensor.
- Further messages: A.82, A.93.
Is it safe?
| Does the heat pump stop? | Yes |
|---|---|
| Engineer needed? | Yes |
The heat pump stops until the fault clears or is reset.
Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).
Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.
What you can check
- On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
- Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
- Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
What the engineer will check
- Check the high pressure sensor and connections X14.1 to X14.3 on the VCMU refrigerant circuit controller:.
- Check wires and plugs for correct seating.
- Check connections for contact corrosion.
- Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
- Check voltage between X14.2/X14.3 in system operation. If it deviates from the curve, replace the high pressure sensor.
- Replace VCMU refrigerant circuit controller.
Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.
Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).
What you might notice
Sources
- Service instructions for contractors: Heat pumps in monoblock design incl. hybrid – System configuration and diagnostics (Vitocal 150-A/151-A/250-A/252-A, IDU-A, AWMOF-151/251, AquaSnap 30AWH, BI-BLOC R290) (6199893 GB 01/2026) ↗ · 6199893 GB 01/2026 (VSA00009) · page 178 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026