F.1006Viessmann · One Base

F.1006 on a Viessmann One Base: Heat pump start count exceeded

Short answer

On a Viessmann heat pump, F.1006 means: Heat pump start count exceeded. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Heat pump start count exceeded.

Part involved: Heat pump start count exceeded.

When it shows: System characteristics: System locked.

Likely causes:

  • Max. number exceeded for following events:.
  • Heating mode: Oil sump temperature higher than secondary circuit flow temperature Cooling mode: Oil sump temperature higher than air intake temperature.
  • Further message: I.130, 3 times.

Is it safe?

Does the heat pump stop?Not stated
SeveritySafety lockout
Engineer needed?Yes

The manual does not say whether the heat pump stops.

Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).

Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.

What you can check

  • On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
  • Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
  • Check the outdoor unit is not blocked by leaves, debris or snow.

What the engineer will check

  • Check the following sensors and connections on the VCMU refrigerant circuit controller:.
  • Heating operation: Secondary circuit flow temperature sensor at X15.3/X15.4.
  • Cooling operation: Air intake temperature sensor at X15.3/X15.4.
  • Oil sump temperature sensor at X20.3/X20.4.
  • Check wires and plugs for correct seating.
  • Check connections for contact corrosion.
  • Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. Check resistor R for NTC 10 kΩ on the disconnected plug. Replace sensor if ….
  • Check 6.3 A fuse at X2.3A/X2.3B of VCMU refrigerant circuit controller. Replace fuse if required. Check relay contact at X4.1/X4.2 on VCMU refrigerant circuit controller ….

Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.

Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.