F.1006 on a Viessmann One Base: Heat pump start count exceeded
Short answer
On a Viessmann heat pump, F.1006 means: Heat pump start count exceeded. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Heat pump start count exceeded.
Part involved: Heat pump start count exceeded.
When it shows: System characteristics: System locked.
Likely causes:
- Max. number exceeded for following events:.
- Heating mode: Oil sump temperature higher than secondary circuit flow temperature Cooling mode: Oil sump temperature higher than air intake temperature.
- Further message: I.130, 3 times.
Is it safe?
| Does the heat pump stop? | Not stated |
|---|---|
| Severity | Safety lockout |
| Engineer needed? | Yes |
The manual does not say whether the heat pump stops.
Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).
Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.
What you can check
- On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
- Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
- Check the outdoor unit is not blocked by leaves, debris or snow.
What the engineer will check
- Check the following sensors and connections on the VCMU refrigerant circuit controller:.
- Heating operation: Secondary circuit flow temperature sensor at X15.3/X15.4.
- Cooling operation: Air intake temperature sensor at X15.3/X15.4.
- Oil sump temperature sensor at X20.3/X20.4.
- Check wires and plugs for correct seating.
- Check connections for contact corrosion.
- Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. Check resistor R for NTC 10 kΩ on the disconnected plug. Replace sensor if ….
- Check 6.3 A fuse at X2.3A/X2.3B of VCMU refrigerant circuit controller. Replace fuse if required. Check relay contact at X4.1/X4.2 on VCMU refrigerant circuit controller ….
Who to ask for: Viessmann-trained heat pump engineer with F-gas certification and R290 (A3 flammable refrigerant) competence.
Certification: F-gas certificate (UK F-gas Regulations; EU 2015/2067 Cat. I cited by Viessmann) plus A3/R290 competence per EN 378-4 or IEC 60335-2-40 Annex HH (6202263 p.2).
What you might notice
Sources
- Service instructions for contractors: Heat pumps in monoblock design incl. hybrid – System configuration and diagnostics (Vitocal 150-A/151-A/250-A/252-A, IDU-A, AWMOF-151/251, AquaSnap 30AWH, BI-BLOC R290) (6199893 GB 01/2026) ↗ · 6199893 GB 01/2026 (VSA00009) · page 176 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026