F.100 on a Viessmann One Base: PlusBus voltage error
Short answer
On a Viessmann heat pump, F.100 means: PlusBus voltage error. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: PlusBus voltage error.
Part involved: PlusBus voltage error.
When it shows: System characteristics:; Electronics modules connected to PlusBus are in emergency mode; No communication possible via PlusBus; Further fault messages may be present: F.91, F.92.
Likely causes:
- PlusBus voltage error: < 10 V.
Is it safe?
| Does the heat pump stop? | Partly |
|---|---|
| Engineer needed? | Yes |
The heat pump keeps running with some functions stopped.
Resetting itself: Not stated per code in Viessmann document 6199893 GB 01/2026 (VSA00009).
Manual reset: User may acknowledge via HMI after noting the code (6249162 p.57); the message returns if the cause persists.
What you can check
- On the HMI, tap the message and "?" to read the system characteristics and Viessmann's user tips; note the code (e.g. F.xxx) and text for your contractor (operating instructions 6249162 p.57).
- Acknowledge the message once via the HMI; do not acknowledge fault messages several times in quick succession (6249162 p.58) - notify your contractor.
- Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
What the engineer will check
- Check the number of connected PlusBus subscribers: Max. 15.
- Total length of the PlusBus cable: < 50 m.
- Check the following connections for the PlusBus:.
- On HPMU electronics module, terminals X2.1/ X2.2.
- Wall mounted indoor unit: Connection on the underside of the appliance, 5-pole connection socket on the right, terminals 74.1/74.2 Floorstanding indoor unit: Terminal area for ….
- Connections to all other PlusBus subscribers.
- Check wires and plugs for correct seating.
- Check connections for contact corrosion.
Who to ask for: Viessmann-trained heat pump engineer / qualified electrician.
Certification: Qualified electrician for work on electrical equipment (Viessmann safety instructions).
What you might notice
Sources
- Service instructions for contractors: Heat pumps in monoblock design incl. hybrid – System configuration and diagnostics (Vitocal 150-A/151-A/250-A/252-A, IDU-A, AWMOF-151/251, AquaSnap 30AWH, BI-BLOC R290) (6199893 GB 01/2026) ↗ · 6199893 GB 01/2026 (VSA00009) · page 126 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026