H98 on a Dimplex LA MI inverter outdoor air-to-water: Refrigerant high pressure overload protection

Short answer

On a Dimplex heat pump, H98 means: Refrigerant high pressure overload protection. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Refrigerant high pressure overload protection.

Part involved: Outdoor high pressure sensor.

When it shows: During heating, pressure >= 4.0 MPa (40 bar) detected by HP sensor.

Likely causes:

  • Insufficient water flow (most likely).
  • Blocked strainer, air, low pressure, pump speed, 2-port valves.
  • Faulty high pressure sensor.
  • Faulty refrigerant PCB.
  • Refrigerant overcharge after recent work.

Is it safe?

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: unknown.

Manual reset: Clear via control panel per Dimplex article (method shown as image).

What you can check

  • Check the heating system pressure gauge reads about 1.0-1.5 bar.
  • Note the code and contact the installer or Dimplex service.

What the engineer will check

  • Isolate the heat pump from mains before any work.
  • Flow checks as H62.
  • Gauge high side: trip below 40 bar indicates sensor/PCB fault (F-Gas).

Who to ask for: refrigeration / heat pump service engineer.

Certification: F-Gas (refrigerant handling) certification for any refrigerant-circuit work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026