F22Dimplex

F22 on a Dimplex heat pump: Power transistor (IPM) overheating - system stopped to protect itself

Short answer

On a Dimplex heat pump, F22 means: Power transistor (IPM) overheating - system stopped to protect itself. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 2 sources

What it means

On the LA MI inverter outdoor air-to-water (LA 6/9/12/16 MI)

The manual says: Power transistor (IPM) overheating - system stopped to protect itself.

Part involved: Outdoor IPM temperature sensor.

When it shows: IPM temperature 95C; 3 times in 30 minutes.

Likely causes:

  • Faulty outdoor fan motor.
  • Faulty outdoor PCB.

On the WPM heat pump manager platform (error-code grouping)

The manual says: Domestic hot water: DHW temperatures in heat pump mode below 35C.

Part involved: DHW circuit / cylinder sensor.

When it shows: Heat pump cannot raise cylinder to at least 35C by compressor alone.

Likely causes:

  • DHW circulating pump flow too low.
  • Heating check valve defective.
  • DHW sensor fault/position.
  • Air in cylinder coil pipework (GDHV).
  • 3-port valve not switching (GDHV).

Is it safe?

On the LA MI inverter outdoor air-to-water (LA 6/9/12/16 MI)

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: unknown.

Manual reset: Clear via control panel per Dimplex article (method shown as image).

On the WPM heat pump manager platform (error-code grouping)

Does the heat pump stop?Partly
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: After rectifying the fault the heat pump can be restarted; switching off the control voltage also acknowledges the fault (WPM Touch p.54). On text-display WPMs press Esc to acknowledge (EconPlus EN-16).

Manual reset: After repair installer resets 'Hot water performance' memory: Menu+Enter > Settings > Hot Water > Reset Max HP (GDHV 79000133011).

What you can check

On the LA MI inverter outdoor air-to-water (LA 6/9/12/16 MI)

  • Check the outdoor unit air flow is not obstructed.
  • Note the code and contact the installer or Dimplex service.

On the WPM heat pump manager platform (error-code grouping)

  • Check the heating system pressure gauge reads 1.0-1.5 bar (GDHV).
  • Note the fault code, the heat pump model (type plate) and controller software version shown in operating data, and contact the installer/Dimplex service.

What the engineer will check

On the LA MI inverter outdoor air-to-water (LA 6/9/12/16 MI)

  • Isolate the heat pump from mains before any work.
  • Check fan motor.
  • Check refrigerant PCB.

Who to ask for: refrigeration / heat pump service engineer.

Certification: F-Gas (refrigerant handling) certification for any refrigerant-circuit work.

On the WPM heat pump manager platform (error-code grouping)

  • Check DHW circulating pump flow and speed.
  • Check check valves and 3-port valve.
  • Bleed air from cylinder coil.
  • Check DHW sensor position/reading.
  • Reset Max HP learning.

Who to ask for: heating engineer.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.