E8 on a Daikin Altherma LT: Input over current

Short answer

On a Daikin heat pump, E8 means: Input over current. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Input over current.

Part involved: power supply / inverter electrical.

When it shows: ■ The following CT input with the compressor running continues for 2.5 seconds. CT input: Above 20 A ■ The system will be shut down if the error occurs 16 times. ■ Clearing condition: Continuous run for about 5 minutes (normal) | The following CT input with the compressor running continues for 2.5 seconds. CT input: Above 20 A The system will be shut down if the error occurs 16 times. 3 3 Clearing condition: Continuous run for about 5 minutes (normal).

Likely causes:

  • Over-current due to compressor failure; Over-current due to defective power transistor; Over-current due to defective inverter main circuit electrolytic capacitor; Over-current due to defective outdoor unit PCB; Error detection due to outdoor unit PCB; Over-current due to short-circuit.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: unknown.

Manual reset: Reset via the remote controller (Inspection/Test button) after the cause is fixed; some codes need a manual reset of the remote-controller memory (service manual section 1.4).

What you can check

  • Read the full error code shown on the user interface and note it, with the date/time, for your installer.
  • Check the heat pump isolator switch(es) and the consumer-unit breaker/RCD for the heat pump are ON. If a breaker or RCD has tripped, do not keep resetting it - leave it and call an engineer.

What the engineer will check

  • Follow the service-manual troubleshooting flow chart for this code: check over-current due to compressor failure; check over-current due to defective power transistor; check over-current due to defective inverter main circuit electrolytic capacitor; check over-current due to defective outdoor unit PCB; check error detection due to outdoor unit PCB; check over-current due to short-circuit.

Who to ask for: Heat pump engineer / qualified electrician.

Certification: Electrical competence to BS 7671 (Part P where applicable) for mains supply work.

What you might notice

What owners and engineers report

2 owner and engineer reports mention this.

  • No heating on the Altherma LT (low temperature split): 1 report
  • Heat pump will not start on the Altherma LT (low temperature split): 1 report

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026