Which RCD type do PV and battery inverters need - Type A or Type B?

Short answer

Use Type B where the inverter or PCE lacks at least simple separation between DC and AC and could feed smooth DC fault current, unless the manufacturer states a Type A is acceptable. A4 reg 570.6.2.2 requires Type B for non-isolated PCE on battery systems. Type AC devices should not protect inverter circuits, and devices must suit bidirectional power flow.

Last checked 24 September 2026 · 2 sources

In more detail

  • IET Wiring Matters Jul 2026 cites 570.6.2.2: Type B for non-isolated PCE.
  • A3:2024 530.3.201 bidirectional/unidirectional device selection.
  • IET position paper: many legacy RCDs are Type AC and unable to handle DC from inverters; many RCBOs not assessed as bidirectional.
  • Plug-in spec: device must limit smooth DC residual current to <=5 mA and not impair upstream RCDs.
  • Section 712 Type B provision (simple-separation exception) not re-read this session.

The facts, dated

  1. 01
    Maximum smooth DC residual current from a plug-in solar device — 5 mA

    standard · GB · checked 24 September 2026 · GOV.UK

  2. 02
    BS 7671 reg requiring Type B RCD for non-isolated PCE (per IET) — 570.6.2.2

    standard · UK · checked 24 September 2026 · IET