Does adding a battery change the network application?
Short answer
Usually yes. The battery's inverter counts toward the same 16 A per phase limit as your solar, so a 3.68 kW solar inverter plus a separate battery inverter normally needs G99 approval before installation. A single hybrid inverter can keep the total within G98 if its output is limited to 3.68 kW.
Last checked 24 September 2026 · 1 source
In more detail
- MIS 3002 5.1.9 note example: 3 kW PV + 3 kW battery on single phase exceeds 16 A so G99 applies.
- G98 aggregates all inverters at one connection point.
The facts, dated
- 013 kW PV plus 3 kW battery on a single-phase supply exceeds 16 A so EREC G99 applies (MIS 3002 example)
standard · GB · checked 24 September 2026 · MCS