IE13SolaX Power · SolaX X1-Hybrid G4

IE13 on a SolaX Power SolaX X1-Hybrid G4: Isolation Fault - insulation fault

Short answer

On a SolaX Power inverter, IE13 means: Isolation Fault - insulation fault. The inverter stops until the fault clears or is reset.

Reviewed 24 September 2026 · 1 source

What it means

The manual says: Isolation Fault - insulation fault.

Part involved: PV array insulation resistance (Riso).

Likely causes:

  • Damaged wire insulation.
  • Moisture.

Is it safe?

Does the inverter stop?Yes
SeverityFault — clears by itself when the condition goes

The inverter stops until the fault clears or is reset.

Resetting itself: often - the inverter retests insulation at each start, so a moisture-related fault can clear later in the day as the array dries and return next damp morning.

Manual reset: no (clears when insulation test passes).

What you can check

  • Read and note the exact code and time from the inverter display or app (screenshot).
  • Note whether it only happens in the morning or after rain - tell the installer.
  • Check the solar/battery AC isolator and the consumer-unit breaker/RCD are ON (do not reset a breaker that trips again immediately).
  • Do not touch panels, DC cables, connectors or the DC isolator.
  • Where the SolaX manual says 'press the ESC key to restart the inverter', a homeowner can do that on the display. Steps that say 'disconnect PV+/PV-/battery' are for the installer only.

What the engineer will check

  • Insulation-resistance test each string PV+ and PV- to earth (per IEC 62446-1 / BS 7671 Section 712).
  • Inspect MC4 connectors, cable damage (rodents/roof edges), water ingress in DC isolators/junction boxes.
  • Check module frame earthing.
  • Disconnect strings one at a time to find the faulty string.

Who to ask for: PV installer with insulation tester.

Certification: Electrician competent in grid-connected PV (BS 7671 Section 712; IET Code of Practice for Grid-connected Solar PV), ideally the original MCS-certified PV installer; brand-approved/trained installer to keep manufacturer warranty.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.