SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Viessmann
EFViessmann · Vitotronic 200

EF on a Viessmann Vitotronic 200: Modbus subscriber

Short answer

On a Viessmann heat pump, EF means: Modbus subscriber. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Modbus subscriber.

Part involved: Modbus subscriber.

Likely causes:

  • Communication with a Modbus subscriber not possible.

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

Resetting itself: Not stated per code; Vitotronic messages remain until the cause is removed and are acknowledged with OK (6150133 p.82). Unremedied acknowledged faults are redisplayed the following day.

Manual reset: Acknowledge with OK on the programming unit (user level permitted per 5817913 p.56-57) after the cause is remedied.

What you can check

  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.

What the engineer will check

  • Check Modbus1 and Modbus 2 subscriber lists ("Service functions" "Modbus1 subscriber" / "Modbus2 subscriber").

Who to ask for: Viessmann-trained heat pump installer/service engineer.

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026