DE on a Viessmann Vitotronic 200: Prot.primry pump/fan2: Compressor heat pump stage 2 stops

Short answer

On a Viessmann heat pump, DE means: Prot.primry pump/fan2: Compressor heat pump stage 2 stops. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Prot.primry pump/fan2: Compressor heat pump stage 2 stops.

Part involved: Prot.primry pump/fan2.

When it shows: Compressor heat pump stage 2 stops.

Likely causes:

  • Primary circuit fault:.
  • Primary circuit pressure switch/frost stat has responded.
  • Primary pump thermal relay, heat pump stage 2 (if installed) has responded.
  • Phase monitor has recognised a fault.
  • Phase monitor faulty.

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

Resetting itself: Not stated per code; Vitotronic messages remain until the cause is removed and are acknowledged with OK (6150133 p.82). Unremedied acknowledged faults are redisplayed the following day.

Manual reset: Acknowledge with OK on the programming unit (user level permitted per 5817913 p.56-57) after the cause is remedied.

What you can check

  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.
  • Check the heating system pressure gauge reading and report a low reading to your contractor; make sure the filling loop is closed.
  • Check the outdoor unit (air source models) is not blocked by leaves, debris or snow.

What the engineer will check

  • Check safety equipment (frost protection brine pressure, frost protection AC-Box) on cross connect PCB, terminals X3.9 and X3.8: See "Cross connect PCB". In systems without ….
  • Reset primary source thermal relay. Check primary pump. Replace primary pump if required. The switching signal can be tested at terminal 214.1: See "Main PCB". ….

Who to ask for: Viessmann-trained heat pump installer/service engineer.

Sources

A code explains what the controller detected, not a confirmed root cause.