Heat pumps · Error codes · Viessmann
D3Viessmann · Vitotronic 200

D3 on a Viessmann Vitotronic 200: Low pressure: Compressor stops

Short answer

On a Viessmann heat pump, D3 means: Low pressure: Compressor stops. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Low pressure: Compressor stops.

Part involved: Low pressure.

When it shows: Compressor stops.

Likely causes:

  • Low pressure fault:.
  • Heat pump faulty.
  • Low pressure switch has responded.
  • Low pressure sensor has reported a fault.
  • Low pressure sensor faulty.
  • : Fan blocked or faulty.

Is it safe?

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated per code; Vitotronic messages remain until the cause is removed and are acknowledged with OK (6150133 p.82). Unremedied acknowledged faults are redisplayed the following day.

Manual reset: Acknowledge with OK on the programming unit (user level permitted per 5817913 p.56-57) after the cause is remedied.

What you can check

  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
  • Check the heating system pressure gauge reading and report a low reading to your contractor; make sure the filling loop is closed.
  • Check the outdoor unit (air source models) is not blocked by leaves, debris or snow.

What the engineer will check

  • Clean the evaporator.
  • : Check fan.
  • : Check pressure gauge, primary pump and shut-off facilities.
  • Check low pressure switch/sensor at the following connections:.
  • Vitocal 100-S/111-S: "LPP" connection on the main PCB: See "Main PCB [7] / [7-1] ".
  • Vitocal 200-A/200-S/222-A/222-S: Connection J10 on EEV PCB: See "EEV PCB [4-3] / [4-4] ".
  • Vitocal 200-A, type AWCI-AC 201.A: Connection J4 on the EEV PCB: See "EEV PCB [2] ".
  • Vitocal 200-G/222-G/300-G/333-G: Connection J10 on EEV PCB: See "EEV PCB [4-6] / [4-7] ".

Who to ask for: Viessmann-trained heat pump engineer with F-gas refrigeration certification.

Certification: F-gas certificate (UK F-gas Regulations; Viessmann: refrigerant work by authorised refrigeration engineers only).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026