SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Viessmann
B2Viessmann · Vitotronic 200

B2 on a Viessmann Vitotronic 200: Fan motor speed monitor faulty

Short answer

On a Viessmann heat pump, B2 means: Fan motor speed monitor faulty. The heat pump keeps running. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 2 sources

What it means

The manuals for this range word it in different ways:

  • Fan motor speed monitor faulty.
  • KM BUS refrig. circ. 2: Refrigerant circuit controller activated;; Energy statement not calculated corlimited compressor operation. If this rectly (see chapter "Diagnosis energy operation is not possible, the compresstatement"). sor ….

Part involved: Fan motor speed monitor faulty; KM BUS refrig. circ. 2.

When it shows: Type "Fault" (S) - triggers "05 Refrigerant circuit" on the heat pump control unit. Heat pump characteristics: Fan off, compressor remains in operation. Refrigerant circuit controller activated;; Energy statement not calculated corlimited compressor operation. If this rectly (see chapter "Diagnosis energy operation is not possible, the compresstatement"). sor shuts down after a few minutes. (cont.).

Likely causes:

  • Fan motor speed monitor faulty.
  • Communication fault with EEV controller (refrigerant circuit controller), heat pump stage 2 (if installed).

Is it safe?

Does the heat pump stop?No
Engineer needed?Yes

The heat pump keeps running.

Resetting itself: Not stated in 6150133.

Manual reset: Refrigerant circuit messages cannot be acknowledged in the message history (6150133 p.155); acknowledge the resulting 05/07/A9 message on the control unit.

What you can check

  • This code is only visible to engineers in the service menu (Diagnosis > Refrigerant circuit > Message history); homeowners see message 05, 07 or A9 - note that code and call your contractor.
  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
  • Check the heating system pressure gauge reading and report a low reading to your contractor; make sure the filling loop is closed.

What the engineer will check

  • Check electrical connection of fan in.
  • heat pump terminal area. Replace fan motor if necessary.
  • If fault persists, notify a specialist.
  • Check KM BUS connection. A fluctuating DC voltage of between approx. 20 V and 30 V can be measured at the KM BUS connection to ….

Who to ask for: Viessmann-trained heat pump engineer with F-gas refrigeration certification; Viessmann-trained heat pump installer/service engineer.

Certification: F-gas certificate (UK F-gas Regulations; Viessmann: refrigerant work by authorised refrigeration engineers only).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026