AF on a Viessmann Vitotronic 200: Cylinder primary pump: Inadequate change of temperature in the DHW cylinder

Short answer

On a Viessmann heat pump, AF means: Cylinder primary pump: Inadequate change of temperature in the DHW cylinder. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Cylinder primary pump: Inadequate change of temperature in the DHW cylinder.

Part involved: Cylinder primary pump.

When it shows: Inadequate change of temperature in the DHW cylinder.

Likely causes:

  • Circulation pump for cylinder heating faulty.
  • Cylinder loading system flow rate too low; cylinder loading pump or 2-way valve on cylinder loading system faulty.

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

Resetting itself: Not stated per code; Vitotronic messages remain until the cause is removed and are acknowledged with OK (6150133 p.82). Unremedied acknowledged faults are redisplayed the following day.

Manual reset: Acknowledge with OK on the programming unit (user level permitted per 5817913 p.56-57) after the cause is remedied.

What you can check

  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.
  • Check the heating system pressure gauge reading and report a low reading to your contractor; make sure the filling loop is closed.

What the engineer will check

  • Measure the voltage at the following connections:.
  • Vitocal 300-A: Connection 224.6, see "Expansion PCB".
  • Other heat pumps: Connection 211.4, see "Main PCB". Check circulation pumps and 2-way valve are mechanically sound. If necessary replace circulation pumps and/or 2-way valve.

Who to ask for: Viessmann-trained heat pump installer/service engineer.

Sources

A code explains what the controller detected, not a confirmed root cause.