SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Viessmann
96Viessmann · Vitotronic 200

96 on a Viessmann Vitotronic 200: Precharge relay open

Short answer

On a Viessmann heat pump, 96 means: Precharge relay open. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 2 sources

What it means

The manuals for this range word it in different ways:

  • Precharge relay open.
  • Ice store absorber circ: No heating of the ice store.

Part involved: Precharge relay open; Ice store absorber circ.

When it shows: Type "Note" (H) - triggers "07 Refrigerant circuit" on the heat pump control unit. Heat pump characteristics: Compressor OFF No heating of the ice store.

Likely causes:

  • Precharge relay open.
  • Insufficient or no heat transfer into the ice store.

Is it safe?

Does the heat pump stop?Yes
SeverityWarning
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated in 6150133.

Manual reset: Refrigerant circuit messages cannot be acknowledged in the message history (6150133 p.155); acknowledge the resulting 05/07/A9 message on the control unit.

What you can check

  • This code is only visible to engineers in the service menu (Diagnosis > Refrigerant circuit > Message history); homeowners see message 05, 07 or A9 - note that code and call your contractor.
  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).

What the engineer will check

  • Replace inverter.
  • Check absorber circuit hydraulics. Charge and vent the absorber circuit if required.
  • Check connection of the absorber circuit pump to the ice store extension. Replace absorber circuit pump if required (see "Ice store extension" installation and service ….

Who to ask for: Viessmann-trained heat pump engineer with F-gas refrigeration certification; Viessmann-trained heat pump installer/service engineer.

Certification: F-gas certificate (UK F-gas Regulations; Viessmann: refrigerant work by authorised refrigeration engineers only).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026