87 on a Viessmann Vitotronic 200: Temperature at compressor motor too high
Short answer
On a Viessmann heat pump, 87 means: Temperature at compressor motor too high. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manuals for this range word it in different ways:
- Temperature at compressor motor too high.
- Temperature at the compressor drive windings too high (> 90 °C).
Part involved: Temperature at compressor motor too high; Temperature at the compressor drive windings too high (> 90 °C).
When it shows: Type "Note" (H) - triggers "07 Refrigerant circuit" on the heat pump control unit. Heat pump characteristics: Compressor OFF.
Likely causes:
- Temperature at compressor motor too high.
- Temperature at the compressor drive windings too high (> 90 °C).
Is it safe?
| Does the heat pump stop? | Yes |
|---|---|
| Severity | Warning |
| Engineer needed? | Yes |
The heat pump stops until the fault clears or is reset.
Resetting itself: Not stated in 6150133.
Manual reset: Refrigerant circuit messages cannot be acknowledged in the message history (6150133 p.155); acknowledge the resulting 05/07/A9 message on the control unit.
What you can check
- This code is only visible to engineers in the service menu (Diagnosis > Refrigerant circuit > Message history); homeowners see message 05, 07 or A9 - note that code and call your contractor.
What the engineer will check
- Test coil resistance at compressor.
- Resistance on all windings should be similar. Replace compressor if necessary.
- No action required.
- If problem recurs: Notify a specialist.
Who to ask for: Viessmann-trained heat pump engineer with F-gas refrigeration certification.
Certification: F-gas certificate (UK F-gas Regulations; Viessmann: refrigerant work by authorised refrigeration engineers only).
What you might notice
Sources
- Service instructions Vitotronic 200 type WO1C heat pump control unit (air/water split & monobloc, brine/water) (6150133, 2023-07) ↗ · 6150133 VSA00004 · pages 159, 164 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026