Heat pumps · Error codes · Viessmann
44Viessmann · Vitotronic 200

44 on a Viessmann Vitotronic 200: Short circuit/lead break, secondary circuit flow temperature sensor (upstream of instantaneous heating water heater)

Short answer

On a Viessmann heat pump, 44 means: Short circuit/lead break, secondary circuit flow temperature sensor (upstream of instantaneous heating water heater). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manuals for this range word it in different ways:

  • Short circuit/lead break, secondary circuit flow temperature sensor (upstream of instantaneous heating water heater).
  • Flow sensor cooling: If "Enable flow temperature sensor cooling circuit 7109" is set to "0", cooling operation is possible, otherwise no cooling.

Part involved: Short circuit/lead break, secondary circuit flow temperature sensor (upstream of instantaneous heating …; Flow sensor cooling.

When it shows: Type "Fault" (S) - triggers "05 Refrigerant circuit" on the heat pump control unit. Heat pump characteristics: Compressor OFF If "Enable flow temperature sensor cooling circuit 7109" is set to "0", cooling operation is possible, otherwise no cooling.

Likely causes:

  • Short circuit/lead break, secondary circuit flow temperature sensor (upstream of instantaneous heating water heater).
  • Short circuit, flow temperature sensor, cooling circuit.

Is it safe?

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated in 6150133.

Manual reset: Refrigerant circuit messages cannot be acknowledged in the message history (6150133 p.155); acknowledge the resulting 05/07/A9 message on the control unit.

What you can check

  • This code is only visible to engineers in the service menu (Diagnosis > Refrigerant circuit > Message history); homeowners see message 05, 07 or A9 - note that code and call your contractor.
  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
  • Check the heating system pressure gauge reading and report a low reading to your contractor; make sure the filling loop is closed.
  • Check the room thermostat/remote control and time-program settings are as expected.

What the engineer will check

  • Vitocal 200-A/222-A: Check resistance value (NTC 10 k Ω) at connection J21 (T1) of the EEV PCB: See "EEV PCB [4-3] / [4-4] ".
  • Vitocal 200-S/222-S: Check resistance value (Pt500A) at connection X25.3/X25.4 of the controller and sensor PCB: See "Controller and sensor PCB".
  • Check resistance value (NTC 10 k) Ω at connection J21 (T1) of the EEV PCB: See "EEV PCB [4-6] / [4-7] ".
  • Check resistance value (NTC 10 k Ω) at plug F14: See "Controller and sensor PCB".

Who to ask for: Viessmann-trained heat pump engineer with F-gas refrigeration certification; Viessmann-trained heat pump installer/service engineer.

Certification: F-gas certificate (UK F-gas Regulations; Viessmann: refrigerant work by authorised refrigeration engineers only).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026