Heat pumps · Error codes · Viessmann
3AViessmann · Vitotronic 200

3A on a Viessmann Vitotronic 200: Safety high pressure switch has responded

Short answer

On a Viessmann heat pump, 3A means: Safety high pressure switch has responded. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manuals for this range word it in different ways:

  • Safety high pressure switch has responded.
  • Evaporator temp.sensr: No central heating or central cooling; only defrosting; The air discharge temperature sensor is used for defrosting the evaporator.

Part involved: Safety high pressure switch has responded.; Evaporator temp.sensr.

When it shows: Type "Fault" (S) - triggers "05 Refrigerant circuit" on the heat pump control unit. Heat pump characteristics: Compressor OFF Type "Fault" (S) - triggers "05 Refrigerant circuit" on the heat pump control unit. Heat pump characteristics: Both compressors OFF No central heating or central cooling; only defrosting; The air discharge temperature sensor is used for defrosting the evaporator.

Likely causes:

  • Safety high pressure switch has responded.
  • Lead break, evaporator air intake temperature sensor.

Is it safe?

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated in 6150133.

Manual reset: Refrigerant circuit messages cannot be acknowledged in the message history (6150133 p.155); acknowledge the resulting 05/07/A9 message on the control unit.

What you can check

  • This code is only visible to engineers in the service menu (Diagnosis > Refrigerant circuit > Message history); homeowners see message 05, 07 or A9 - note that code and call your contractor.
  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
  • Check the outdoor unit (air source models) is not blocked by leaves, debris or snow.

What the engineer will check

  • As for "C9 Refrigerant circ (SHD)" : See "Message overview" for the heat pump control unit.
  • Check resistance value Pt500A at the connection on the EEV PCB: See "EEV PCB [2] ".
  • Vitocal 100-S/111-S: Check resistance value NTC 15 k Ω at the connection on the main PCB of the outdoor unit: See "Main PCB [7] / ….

Who to ask for: Viessmann-trained heat pump engineer with F-gas refrigeration certification; Viessmann-trained heat pump installer/service engineer.

Certification: F-gas certificate (UK F-gas Regulations; Viessmann: refrigerant work by authorised refrigeration engineers only).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026