21Viessmann · Vitotronic 200

21 on a Viessmann Vitotronic 200: Inadequate evaporation pressure (low pressure fault)

Short answer

On a Viessmann heat pump, 21 means: Inadequate evaporation pressure (low pressure fault). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manuals for this range word it in different ways:

  • Inadequate evaporation pressure (low pressure fault).
  • Return sensor secndry: Operation with temperature value of flow temperature sensor in secondary circuit, minus 5 K.; If the secondary circuit flow and return temperature sensors are faulty at the ….

Part involved: Inadequate evaporation pressure (low pressure fault); Return sensor secndry.

When it shows: Type "Note" (H) - triggers "07 Refrigerant circuit" on the heat pump control unit. Heat pump characteristics: Compressor OFF Type "Note" (H) - triggers "07 Refrigerant circuit" on the heat pump control unit. Heat pump characteristics: Both compressors OFF Operation with temperature value of flow temperature sensor in secondary circuit, minus 5 K.; If the secondary circuit flow and return temperature sensors are faulty at the same time, the heat pump is switched off. After 24 h the message ….

Likely causes:

  • Inadequate evaporation pressure (low pressure fault).
  • Short circuit, secondary circuit return temperature sensor.

Is it safe?

Does the heat pump stop?Yes
SeverityWarning
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated in 6150133.

Manual reset: Refrigerant circuit messages cannot be acknowledged in the message history (6150133 p.155); acknowledge the resulting 05/07/A9 message on the control unit.

What you can check

  • This code is only visible to engineers in the service menu (Diagnosis > Refrigerant circuit > Message history); homeowners see message 05, 07 or A9 - note that code and call your contractor.
  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.
  • Check the heat pump breaker/isolator in the consumer unit is ON (do not repeatedly reset a breaker or RCD that keeps tripping).
  • Check the heating system pressure gauge reading and report a low reading to your contractor; make sure the filling loop is closed.

What the engineer will check

  • As for "D3 Low pressure" : See "Message overview" for the heat pump control unit.
  • Check resistance value (Pt500A) at terminals X25.11/ X25.12: See "Controller and sensor PCB".

Who to ask for: Viessmann-trained heat pump engineer with F-gas refrigeration certification; Viessmann-trained heat pump installer/service engineer.

Certification: F-gas certificate (UK F-gas Regulations; Viessmann: refrigerant work by authorised refrigeration engineers only).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026