SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Viessmann
02Viessmann · Vitotronic 200

02 on a Viessmann Vitotronic 200: Short circuit/lead break, air discharge temperature sensor

Short answer

On a Viessmann heat pump, 02 means: Short circuit/lead break, air discharge temperature sensor. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manuals for this range word it in different ways:

  • Short circuit/lead break, air discharge temperature sensor.
  • Data error stand.settg.

Part involved: Short circuit/lead break, air discharge temperature sensor; Data error stand.settg.

When it shows: Type "Fault" (S) - triggers "05 Refrigerant circuit" on the heat pump control unit. Heat pump characteristics: Operation with temperature value of flow temperature sensor in primary circuit, minus 2 K.

Likely causes:

  • Short circuit/lead break, air discharge temperature sensor.
  • Delivered condition set after recognition of data error.

Is it safe?

Does the heat pump stop?Partly
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: Not stated in 6150133.

Manual reset: Refrigerant circuit messages cannot be acknowledged in the message history (6150133 p.155); acknowledge the resulting 05/07/A9 message on the control unit.

What you can check

  • This code is only visible to engineers in the service menu (Diagnosis > Refrigerant circuit > Message history); homeowners see message 05, 07 or A9 - note that code and call your contractor.
  • Note the 2-character message code and message text shown on the Vitotronic 200 display (press OK for details) and give them to your heating contractor (operating instructions 5817913 p.56).
  • You may acknowledge the message once with OK as described in the Vitotronic 200 operating instructions; if it reappears, do not keep acknowledging it - call your contractor.

What the engineer will check

  • Check resistance value (Pt500A) at the sensor connection of the EEV PCB: See "EEV PCB [2] ".
  • Reconfigure system.

Who to ask for: Viessmann-trained heat pump engineer with F-gas refrigeration certification; Viessmann-trained heat pump installer/service engineer.

Certification: F-gas certificate (UK F-gas Regulations; Viessmann: refrigerant work by authorised refrigeration engineers only).

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026