F23 on a Toshiba heat pump: Low pressure sensor failure

Short answer

On a Toshiba heat pump, F23 means: Low pressure sensor failure. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 4 sources

What it means

On the R32 Estia 1-Series (split, Wall-Mounted and All-in-One)

The manual says: Low pressure sensor failure.

Part involved: refrigerant charge, PMV, valves, pressure switch/sensor.

When it shows: Open circuit in low pressure sensor.

Likely causes:

  • Low pressure sensor body/wiring.
  • Refrigerant gas leak.

On the Estia (Series 4) Standard & Powerful

The manual says: Low pressure sensor error.

Part involved: refrigerant charge, PMV, valves, pressure switch/sensor.

When it shows: PS < 0.07 MPa for 90 s (cooling/defrost) or 10 min (heating/DHW).

Likely causes:

  • Low pressure sensor body/wiring.
  • Sensor resistance.
  • Refrigerant gas leak.

On the Estia 5 Series (Standard)

The manual says: Low pressure sensor error.

Part involved: refrigerant charge, PMV, valves, pressure switch/sensor.

When it shows: PS < 0.07 MPa for 90 s (cooling/defrost) or 10 min (heating/DHW).

Likely causes:

  • Low pressure sensor body/wiring.
  • Sensor resistance.
  • Refrigerant gas leak.

On the Estia 5 Series Powerful (Hi Power / Extreme)

The manual says: Low pressure sensor error.

Part involved: refrigerant charge, PMV, valves, pressure switch/sensor.

When it shows: Trigger thresholds not printed in the IM; see SM.

Likely causes:

  • Low pressure sensor body/wiring.
  • Sensor resistance.
  • Refrigerant gas leak.

Is it safe?

Does the heat pump stop?Partly
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: yes (per manual).

Manual reset: Clear the code from the remote controller once the cause is fixed (service procedure).

What you can check

  • Note the check code shown on the remote controller and the outdoor/hydro model numbers before contacting an engineer.
  • Check the outdoor unit is not blocked by leaves, debris, snow or ice, and that nothing is covering the air inlet/outlet.

What the engineer will check

On the R32 Estia 1-Series (split, Wall-Mounted and All-in-One)

  • Follow manufacturer's check-code flowchart.
  • Low pressure sensor body/wiring.
  • Refrigerant gas leak.

Who to ask for: F-gas certified refrigeration / heat pump engineer.

Certification: F-gas Category I; R32 is A2L mildly flammable - trained handler required.

On the Estia (Series 4) Standard & Powerful

  • Follow manufacturer's check-code flowchart.
  • Low pressure sensor body/wiring.
  • Sensor resistance.
  • Refrigerant gas leak.

Who to ask for: F-gas certified refrigeration / heat pump engineer.

Certification: F-gas Category I; R32 is A2L mildly flammable - trained handler required.

On the Estia 5 Series (Standard)

  • Follow manufacturer's check-code flowchart.
  • Low pressure sensor body/wiring.
  • Sensor resistance.
  • Refrigerant gas leak.

Who to ask for: F-gas certified refrigeration / heat pump engineer.

Certification: F-gas Category I; R32 is A2L mildly flammable - trained handler required.

On the Estia 5 Series Powerful (Hi Power / Extreme)

  • Follow manufacturer's check-code flowchart.
  • Low pressure sensor body/wiring.
  • Sensor resistance.
  • Refrigerant gas leak.

Who to ask for: F-gas certified refrigeration / heat pump engineer.

Certification: F-gas Category I; R32 is A2L mildly flammable - trained handler required.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.