Heat pumps · Error codes · LG
CH01LG

CH01 on a LG heat pump: Problem in remote (room) air temperature sensor – sensor on the indoor Main PCB/remote room sensor is open or short circuit

Short answer

On a LG heat pump, CH01 means: Problem in remote (room) air temperature sensor – sensor on the indoor Main PCB/remote room sensor is open or short circuit. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 2 sources

What it means

On the LG, all models

The manual says: Problem in remote (room) air temperature sensor – sensor on the indoor Main PCB/remote room sensor is open or short circuit.

Part involved: room air temperature sensor (CN_ROOM).

When it shows: Room air sensor reading open/short (normal: 10 kΩ at 25 °C unplugged, ~2.26 V DC plugged).

Likely causes:

  • Incorrect connection between sensor and PCB; indoor Main PCB fault; sensor failure; temperature sensor limit reached.

On the THERMA V Water Heater (heat pump DHW cylinder)

The manual says: Ambient temperature sensor is not working (THERMA V water heater).

Part involved: thermistor.

When it shows: Ambient temperature sensor is not working.

Likely causes:

  • Ambient temperature sensor is not working.

Is it safe?

On the LG, all models

Does the heat pump stop?Partly
SeverityWarning
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: yes – trouble clears when the condition is repaired; emergency operation must be restarted by the user after a power reset.

Manual reset: Not normally required; user restarts after power reset if emergency operation was running.

On the THERMA V Water Heater (heat pump DHW cylinder)

Does the heat pump stop?Partly
SeverityWarning
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: unknown.

Manual reset: Per LG corrective action; service engineer for most codes.

What you can check

On the LG, all models

  • Read the code on the controller (LG shows 'CH' + number; older wired controllers alternate 'CH' and the number) and note it together with the model number. Report it to your installer or an LG-authorised service centre – LG owner's manuals say an error code generated by self-diagnosis is a reason to call the service. For this 'trouble' class LG allows temporary emergency operation: if the controller shows a pop-up offering it you may accept (OK) as a stop-gap; running costs will be higher, so do not use it long term. Emergency operation does not restart by itself after a power cut – you must switch it back on at the controller. If a wireless/wired room sensor or thermostat is fitted, check its batteries/display and settings.

On the THERMA V Water Heater (heat pump DHW cylinder)

  • Note the code shown on the water heater display. LG's corrective action: call LG technical support. While the fault is present the unit operates as: Use elements only – hot water will be heated more slowly/at higher cost.

What the engineer will check

On the LG, all models

  • Check the thermistor is fully inserted in its pocket/holder and the connector is seated on the correct PCB header; measure resistance unplugged (LG: pipe/water sensors 5 kΩ at 25 °C, room air sensor 10 kΩ at 25 °C, D-pipe sensor ~200 kΩ at 25 °C) and voltage plugged (~2.2–2.5 V DC at 25 °C) against LG resistance-temperature tables; replace sensor, then PCB if readings are correct.

Who to ask for: Heat pump engineer (controls, sensors, PCB).

Certification: None statutory beyond electrical competence (BS 7671).

On the THERMA V Water Heater (heat pump DHW cylinder)

  • Check the thermistor is fully inserted in its pocket/holder and the connector is seated on the correct PCB header; measure resistance unplugged (LG: pipe/water sensors 5 kΩ at 25 °C, room air sensor 10 kΩ at 25 °C, D-pipe sensor ~200 kΩ at 25 °C) and voltage plugged (~2.2–2.5 V DC at 25 °C) against LG resistance-temperature tables; replace sensor, then PCB if readings are correct.

Who to ask for: Heat pump engineer / electrician (inverter and PCB diagnostics).

Certification: Competent person for electrical work (BS 7671); isolate and wait 3 min for DC-link discharge.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026