Heat pumps · Error codes · IVT
EKIVT · Greenline HT Plus

EK on an IVT Greenline HT Plus: Electric cassette (EK) alarm: the electric additional heater miniature circuit-breaker or overheat protection has tripped

Short answer

On an IVT heat pump, EK means: Electric cassette (EK) alarm: the electric additional heater miniature circuit-breaker or overheat protection has tripped. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Electric cassette (EK) alarm: the electric additional heater miniature circuit-breaker or overheat protection has tripped.

Part involved: electric cassette MCB (fuse 3) / overheat protection (fuse 4).

Likely causes:

  • Electric cassette MCB tripped; electric cassette overheat protection tripped - most frequently due to poor flow over the cassette (air in heat pump or clogged particle filter).

Is it safe?

Does the heat pump stop?Partly
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Manual reset: Ackn. button on Rego 637 control panel.

What you can check

  • Press the Ackn. button on the control panel once (the manual says there is no risk in resetting an alarm; the heat pump restarts within 15 minutes if heat is needed). If the alarm returns, contact your installer. Check the heating-system pressure gauge is in the range given in the user guide (Thermia/Danfoss: 1-1.5 bar when cold) - do not top up yourself unless you have been shown how; check radiator/underfloor valves and room thermostats are open.

What the engineer will check

  • Reset cassette MCB (circuit breaker 3) and overheat protector (button 4, press firmly); clean hot-side particle filter; vent; investigate repeated trips.

Who to ask for: heat pump engineer.

Certification: Qualified electrician / heat pump engineer (electrical fault-finding).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026