Short answer
On a Daikin heat pump, 7H-05 means: Water flow problem during heating/sampling. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Water flow problem during heating/sampling.
Part involved: water flow / circulation pump / flow sensor.
When it shows: Water flow abnormality determined mainly during space heating.
Likely causes:
- Closed stop valve in the water circuit.; Air in the water circuit.; Water flow is too low.; Water pressure is too low.; No by‑pass installed in the water circuit.; Faulty water flow sensor.; Faulty 3‑way valve.; Faulty water pump.; Faulty hydro PCB.
Is it safe?
| Does the heat pump stop? | Yes |
|---|---|
| Severity | Fault — needs a manual reset once the cause is fixed |
| Engineer needed? | Yes |
The heat pump stops until the fault clears or is reset.
Resetting itself: no.
Manual reset: Manual reset via user interface.
What you can check
- Read the full error code and sub-code shown on the user interface (Malfunctioning screen; press the help button for Daikin's long description) and note it, with the date/time, for your installer.
- Check the heating-system water pressure reading on the gauge/display: Daikin operation manuals ask users to check it is above 1 bar. If it is below that, report it to your installer (do not open the unit).
- Do NOT bleed radiators while an error/malfunction symbol is displayed: Daikin operation manuals warn refrigerant may have leaked into the water circuit - ventilate and call your installer.
- If heating/hot water has stopped, the operation manual lets the user confirm on the Malfunctioning screen whether the backup/booster heater may take over as emergency heating (much higher running cost) until the installer attends.
What the engineer will check
- Check that all stop valves of the water circuit are open. . ; Purge the water circuit. . ; Check the water flow. . ; Check the water pressure. . ; Check if a by‑pass is installed in the water circuit. . ; Perform an electrical check of the water flow sensor. . ; Perform a check of the 3-way valve. . ; Perform a check of the water pump. . ; Perform a check of the hydro PCB. . ; | Troubleshooting.
Who to ask for: Heat pump installer / heating engineer.
Certification: None specific for water-side checks; MCS-certified installer recommended.
What you might notice
What owners and engineers report
13 owner and engineer reports mention this.
- No heating on the Altherma: 7 reports
- Keeps stopping / cutting out on the Altherma: 2 reports
- No hot water on the Altherma: 2 reports
- Radiators cold on the Altherma: 2 reports
Sources
- Service manual Daikin Altherma 3 M EBLA/EDLA04~08E (ESIE22-09) ↗ · ESIE22-09 · page 21 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.